Vibration Level Switch LVL-M2C
SI00113O-G
20
22
-0
3
25
EN
11
Connection Data
Basic specification, feature Electrical connection, option SI, N1, N2
Associated intrinsically safe power supply unit with max. electrical specifications below
the characteristic values of the electronic inserts
Table 5
Basic specification, feature Electrical connection, option PA
Certified intrinsically safe fieldbus (PROFIBUS PA), in accordance with the FISCO model,
with the following maximum values
Table 6
Certified intrinsically safe circuit with the following maximum values
Table 7
Electrical connection
Electronic insert
Supply
SI
FEL55
U
i
P
i
I
i
C
i
L
i
= 36 V
= 1 W
= 100 mA
= 0
= 0
N1
FEL56
U
i
P
i
I
i
C
i
L
i
= 16 V
= 170 mW
= 52 mA
= 30 nF
= 0
N2
FEL58
U
i
P
i
I
i
C
i
L
i
= 16 V
= 170 mW
= 52 mA
= 30 nF
= 0
Electrical connection
Electronic insert
Supply
PA
FEL50A
U
i
P
i
I
i
C
i
L
i
= 17.5 V
= 5.5 W
= 500 mA
= 2,7 nF
=
10
H
Electrical connection
Electronic insert
Supply
PA
FEL50A
U
i
P
i
I
i
C
i
L
i
= 24 V
= 1.2 W
= 250 mA
= 2.7 nF
=
10
H