VBA-2E-G11-I/U/PT100-*
Commissioning
6
Commissioning
6.1
Assigning an Address to the Module
To operate the VBA-2E-G11-I/U/PT100-* in an AS-Interface network, you must assign a
suitable address to the AS-Interface slave. The AS-Interface VBP-HH1-V3.0 handheld device
by Fuchs or an AS-Interface master can be used to assign addresses.
The VBA-2E-G11-I/U/PT100-* module is a standard slave as defined by specification 2.1.
These modules can be assigned addresses 1 to 31. The default address on delivery is 0.
6.2
Slave Profile
The VBA-2E-G11-I/U/PT100-* has the profile
S-7.3.D
The data value is transmitted as defined by AS-Interface profile 7.3.
6.3
Parameterization
The following parameters can be set for the VBA-2E-G11-I/U/PT100-*. Program the
parameters using an AS-Interface master, with the VAZ-SW-ACT32 AS-i Control Tool from
Fuchs or with the VBP-HH1-V3.0 handheld device.
Parameter P0: 50/60 Hz Filter
Default value P0=1, active
With parameter P0, you activate the filter for 50/60 Hz power frequencies. With an activated
filter, power frequency interference is suppressed. In this case, the conversion time is extended
(see chapter 9.2).
Parameter P1: Second Channel
Default value P1=1, active
Parameter P1 is used to switch the second measuring channel on or off. If the second channel
is switched off, this can considerably reduce the conversion time in the module. (see chapter
9.2)
Alternatively, it is possible to control the second channel via the bridges on input PT2. (see
chapter 4.2)
I/O
=
7
ID
=
3
ID1
=
F (programmable)
ID2
=
D
Note!
The bridges on input PT2 override parameter P1.