In this chapter, you learn everything necessary to run the AS-i/PROFIBUS Gateway
in a Profibus-DP network.
For data exchange on Profibus-DP there are three operation modes: the easy mode,
the advanced mode and the professional mode (advanced mode with management
channel).
The following table shows the differences between the three modes:
Hint: If you try to put an AS-i/PROFIBUS Gateway in operation the first
time it is advisable to use the easy mode because it is much easier than
the advanced modes.
following Functions are available
in easy mode
in advanced
mode
in professional
mode
Transmission of AS-i input and
outut data
X
X
X
AS-i circuit can be configured
locally on the gateway
X
-
X
Putting into Operation without addi-
tional parameterization of the Profi-
bus master
X
-
-
Working with a standard I/O-config-
uration on Profibus-DP
X
-
-
Detection of AS-i errors via DP-
diagnosis
X
X
X
Transmission of AS-i parameters to
the gateway while the system is
running (e.g. switching of the mea-
surement range of sensors)
-
X
X
Configuring and parameterizing the
AS-i circuit by the DP-master
-
X
X
Reading and Writing AS-i Control
programs via Profibus-DP
-
X
-
AS-i Transmission of user flags for
the AS-i Control program via Profi-
bus DP
-
X
X
Adjust the size of the I/O windows
to the actual extension of the AS-i
circuit
-
X
X
Transmission of additional AS-i
commands and advanced diagnosis
-
X
X