Commissioning
Programming mode activation
The switchover from normal mode to parameterization mode is made by pressing button 2 on
the back of the read head.
Parameterization Mode Activation
1. Press button 2 for longer than 2 s.
Yellow LED3 now flashes.
2. Hold the "ENABLE" code in front of the camera system on the read head to trigger final
activation
If the "ENABLE" activation code is detected, the green LED2 lights up for 1 sec. If the
activation code is not detected, LED2 lights up red for 2 seconds.
Parameterization
Place the parameterization code in the field of vision of the camera module.
After the parameterization code is detected, the green LED2 lights up for 1 sec. In the event
of an invalid parameterization code, LED2 lights up red for 2 seconds.
Exiting Parameterization Mode
Hold the "STORE" code in front of the camera system on the read head to save the
configuration
When the "STORE" memory code is detected, the green LED2 lights up for 1 sec. The
parameterization is stored in the nonvolatile memory of the read head and parameterization
mode is terminated. Parameterization of the read head is now complete. If the memory code is
not detected, LED2 lights up red for 2 seconds.
The code cards "CANCEL", "USE", and "DEFAULT"
Holding one of these cards in front of the reading head exits parameterization mode with the
following consequences:
■
CANCEL:
All parameter changes that are made but have not yet been saved are discarded. The
reading head operates with the last valid parameters that were saved.
■
USE:
For test purposes, the reading head operates with the parameters that have just been
modified. The parameterization is not saved, however. After being switched off and on
again, the reading head operates with the last valid parameters that were saved.
■
DEFAULT:
All parameters in the reading head are overwritten with the original default settings. Re-
enter the configuration mode and save the default settings nonvolatile with the code card
STORE.
Note!
External parameterization of the read head using code cards must be started within 10 minutes
of the read head switching on. A time lock disables the read head once this time has elapsed.
The time lock remains inactive during the parameterization process. The time lock disables the
read head only if no parameterization activities take place for more than 10 minutes.
If a button is pressed when the time lock is enabled, all LEDs flash and remain lit for 2 seconds
during each flashing cycle.
Note!
Press button 2 briefly to exit parameterization mode. Any parameter changes that are made but
have not yet been saved are discarded. The read head operates with the last valid parameters
that were saved.