Commissioning

 2

0

1

8

-0

3

19

Changing the device name

1. Stop PROFINET communication if it is active.

2. Select 

Fuchs WCS

 from the list of nodes and click on 

OK

.

3. In the field 

Assign device name

, enter the device name for the interface module. Click on 

Assign Name

.

 The interface module is given the name you entered and can then be uniquely identified 

by the PLC.

4. In the WCS module 

Properties

 window, enter the new device name and save the 

configuration.

 The PLC will recognize the name of the device and will be able to communicate with it.

Depending on your application, select one, two, three, or four connected WCS readers and the 
operating mode. When in the "only Position" operating mode, the WCS readers output their 
position. In the "Position and Speed" operating mode, the WCS readers output their position 
and the speed at which they are currently moving.

Regardless of the number of WCS readers, 1 byte is reserved for querying the diagnosis of the 
WCS readers in the master. For the response data, 4 bytes are reserved per WCS reader in the 
"only Position" operating mode (configuration data for 4 WCS readers: 0x20, 0xD1, 0xD1, 
0xD1, 0xD1). In the "Position and Speed" operating mode, 6 bytes are reserved per WCS 
reader (configuration data for 4 WCS readers: 0x20, 0xD2, 0xD2, 0xD2, 0xD2).

Note!

The PLC must not communicate with the device via PROFINET while you are changing the 
device name. An error message will be output if you try to change the device name while the 
plant is in operation.

Note!

An LED on the device can be made to flash using the configuration tools. If you have a number 
of WCS-PNG210 interface modules on the network, this function will enable to you to uniquely 
identify each device. Select the device from the list of Ethernet modules and click on 

Flash

The "State" LED on the relevant WCS-PNG210 interface module will start to flash.

Summary of Contents for PROFINET WCS-PNG210

Page 1: ...WCS PNG210 WCS PROFINET IO Interface Module FACTORY AUTOMATION MANUAL...

Page 2: ...Terms of Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in i...

Page 3: ...gn of the Device 7 3 Installation 10 3 1 Mounting 10 3 2 Electrical Connection 11 3 3 Dismounting 13 4 Commissioning 15 4 1 Introduction 15 4 2 Connecting WCS Readers 16 4 3 Connecting the WCS PNG210...

Page 4: ...licable EU type examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Instruction manual Other documents 1 2 Target Group Personnel Responsibilit...

Page 5: ...in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indicat...

Page 6: ...CS reader and WCS PNG210 is transmitted via an RS 485 interface The data from the WCS PNG210 to the controller is transmitted via the PROFINET protocol You can connect a maximum of four WCS readers of...

Page 7: ...omponents Figure 2 2 Interface module overview 1 X1 RS 485 interface 2 RS 485 bus termination slide switch 3 Mounting bracket 4 X2 Connection for power supply 5 X3 PROFINET IO communication interface...

Page 8: ...der address 8 4 2 1 0 0 0 1 0 0 0 1 0 1 0 1 0 0 2 1 0 0 0 3 Table 2 1 Display of the four LEDs Error No Select ID when the State LED lights up green Error No 1 5 Switch the interface module off and ba...

Page 9: ...fic on the network the LED flashes green at the same speed as the sent received data 0 1 0 1 5 Script error 0 1 1 0 6 Reserved 0 1 1 1 7 Communication WCS reader RS send buffer overflow 1 0 0 0 8 Comm...

Page 10: ...to place The module is mounted 2 You must connect the DIN mounting rail to the switch cabinet s equipotential busbar The connection wire must have a cross section of at least 10 mm2 2 1 Note Heat diss...

Page 11: ...e not be plugged in incorrectly Danger Device damage due to incorrect installation A faulty installation of cables and connection lines can endanger the function and the electrical safety of the devic...

Page 12: ...label RJ45 PROFINET IO Preparing to use the RS 485 interface For operation on an RS 485 interface the terminal on connector X1 must be connected as follows 1 Connect terminal 4 Rx 422 to terminal 6 T...

Page 13: ...422 Termination to Off and the slide switch Tx 422 Termination to On This activates the RS 485 terminator 150 built into the interface module If you only connect one WCS reader to the interface module...

Page 14: ...ule 1 Disconnect all the supply and signal lines Figure 3 3 Dismounting 2 Insert the screwdriver 2 into the groove of the mounting bracket 3 3 Press the screwdriver 2 in the specified direction until...

Page 15: ...ting rail onto which the assembly is snapped 6 Connect the direct current to the terminals provided 7 Use any planning tool for project planning The GSDML file can be downloaded from our website www p...

Page 16: ...4 4 3 Connecting the WCS PNG210 to the network The connection to the PROFINET IO is made via the two RJ45 PROFINET IO sockets on the underside of the interface module The front socket is labeled X3 P...

Page 17: ...not yet have a device name The device name is assigned to the module via the project planning software The following rules from the PROFINET specification apply to the device name It consists of one o...

Page 18: ...ield Devices Gateway Pepperl Fuchs WCS 4 Drag the WCS PNG210 from the tree structure and drop it into your PROFINET IO system The symbol for the WCS PNG210 is shown in the PROFINET IO system 5 Double...

Page 19: ...speed at which they are currently moving Regardless of the number of WCS readers 1 byte is reserved for querying the diagnosis of the WCS readers in the master For the response data 4 bytes are reser...

Page 20: ...window where the modules are listed The selected module is added to the list 4 To change the input and output address of the module double click on the module and enter the addresses in the Properties...

Page 21: ...A1 A0 Byte 4 0 0 0 0 0 0 0 0 Byte 5 0 S06 S05 S04 S03 S02 S01 S00 Table 4 4 Data format for each connected WCS reader in Position and Speed operating mode reader address 0 3 A1 A0 Reader address 0 0...

Page 22: ...s connected at the beginning and one device is connected at the end of the data line Figure 5 1 Connection of one reading head If two WCS readers are connected to one interface module there are two wi...

Page 23: ...ng of the data line one WCS reader is located at the end of the data line Both need the RS 485 terminator The second WCS reader is connected to the line connection between the interface module and the...

Page 24: ...ion B The wiring version used depends on which is best suited for the application If three or four WCS readers are used on the same interface module connect these using spurs as shown in variant B Rea...

Page 25: ...heating six wire data cable 3 x 2 can be used These data cables use two pairs for the power supply doubling the cable cross section and one pair for the RS 485 data line The table shows the possible...

Page 26: ...mm 8 mm V1 W PG9 straight 5 6 mm 8 mm V15 G PG9 angled 5 6 mm 8 mm V15 W PG9 straight 6 6 mm 8 mm V17 G PG9 angled 6 6 mm 8 mm V17 W PG9 Table 5 1 Cable outlet on top not variable Number of poles Cab...

Page 27: ...GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia Paci...

Reviews: