background image

 2

02

0-

05

18

Functional Safety KFD2-SR2-Ex*.W(.LB)

Operation

5.1.1

Procedure for Manual Proof Test

Equipment required:

Digital multimeter with an accuracy of 0.1 %

Use for the proof test of the intrinsic safety side of the device a special digital multimeter 

for intrinsically safe circuits.
If intrinsically safe circuits are operated with non-intrinsically safe circuits, they must 

no longer be used as intrinsically safe circuits.

Power supply set to nominal voltage of 24 V DC

Simulate the sensor state by a potentiometer of 4.7 k

 (threshold for normal operation), 

by a resistor of 220

 (short circuit detection) and by a resistor of 150 k

 

(lead breakage detection).

Proof Test Procedure

1.

Put out of service the entire safety loop. Protect the application by means of other measures.

2.

Prepare a test set-up, see figures below.

3.

Simulate the sensor state by connecting a potentiometer, a resistor for short circuit detection 

or by a resistor for lead breakage detection.

Test each input channel individually.

4.

Connect a potentiometer of 4.7 k

 (threshold for normal operation) to the input.

 The threshold must be between 1.4 mA and 1.9 mA, the hysteresis must be between 

170

µ

A and 250

µ

A.

• If the input current is above the threshold the relay must be activated for normal mode 

of operation. The yellow LED lights up.

• If the input current is below the threshold the relay must be activated for inverted mode 

of operation. The yellow LED lights up.

5.

Connect a resistor R

SC

 (220

) or a resistor R

LB

 (150 k

) to the input.

 The device must detect an external fault. This state is indicated by red LED and the relay 

of the corresponding output must be de-activated.

6.

Test all relay outputs with a specific current, e. g. 100 mA. To avoid electric shock, 

use a test voltage of 24 V DC. Check that the relay contacts are open.

 The relays must be de-activated. The relay contacts must 

definitely open

.

7.

Set back the device to the original settings for the current application after the test.

8.

Check the correct behavior of the safety loop. Is the configuration correct?

9.

Secure the DIP switches to prevent unintentional adjustments.

Summary of Contents for KFD2-SR2-Ex Series

Page 1: ...ISO9001 2 Functional Safety Switch Amplifier KFD2 SR2 Ex W LB Manual...

Page 2: ...ion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs co...

Page 3: ...Function 8 2 3 Interfaces 9 2 4 Marking 9 2 5 Standards and Directives for Functional Safety 9 3 Planning 10 3 1 System Structure 10 3 2 Assumptions 11 3 3 Safety Function and Safe State 12 3 4 Charac...

Page 4: ...Functional Safety KFD2 SR2 Ex W LB Contents 4 2020 05...

Page 5: ...ting Dismounting Disposal The documentation consists of the following parts Present document Instruction manual Manual Datasheet Additionally the following parts may belong to the documentation if app...

Page 6: ...nd understood the instruction manual and the further documentation Intended Use The device is only approved for appropriate and intended use Ignoring these instructions will void any warranty and abso...

Page 7: ...re displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This sy...

Page 8: ...om NAMUR sensors or dry contacts from the hazardous area to the non hazardous area The proximity sensor or switch controls a change over relay contact for the load in the non explosion hazardous area...

Page 9: ...Directives for Functional Safety Device specific standards and directives System specific standards and directives Note For corresponding connections see datasheet Pepperl Fuchs Group Lilienthalstra e...

Page 10: ...he demand rate for this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault reaction...

Page 11: ...must be multiplied by a factor of 2 5 based on experience A similar factor must be used if frequent temperature fluctuations are expected SIL 2 application To build a SIL safety loop for the defined...

Page 12: ...fe state is reached if the NAMUR sensor input is in the on state S2 position I output II as signal output Output II has the same switching state like output I S2 position II output II as fault indicat...

Page 13: ...sions are supervised The line fault detection is activated if switch S3 is in position I The related safety function is defined as the outputs are de energized safe state if there is a line fault dete...

Page 14: ...oof test In loop proof test PTC 100 90 PFDavg for T1 1 year 3 1 65 x 10 4 3 15 x 10 4 PFDavg for T1 2 years 3 3 31 x 10 4 4 64 x 10 4 PFDavg for T1 3 years 3 4 96 x 10 4 6 13 x 10 4 Fault reaction tim...

Page 15: ...o the following conditions highly stressful environmental conditions such as constantly high temperatures temperature cycles with high temperature differences permanent repeated mechanical stress vibr...

Page 16: ...n 5 Check the safety function to ensure the expected output behavior 4 1 Configuration Configuring the Device The device is configured via DIP switches The DIP switches for setting the safety function...

Page 17: ...n of the respective effectiveness e g concepts according to NA106 2018 According to IEC EN 61508 2 a recurring proof test shall be undertaken to reveal potential dangerous failures that are not detect...

Page 18: ...ge detection Test each input channel individually 4 Connect a potentiometer of 4 7 k threshold for normal operation to the input The threshold must be between 1 4 mA and 1 9 mA the hysteresis must be...

Page 19: ...Zone 0 1 2 Div 1 2 Zone 2 Div 2 KFD2 SR2 Ex1 W Multimeter mA Multimeter mA 240 2 5 W 24 V DC 2 3 1 7 8 9 I supply 14 15 RLB 24 V DC Power supply Supply RSC Multimeter mA Zone 0 1 2 Div 1 2 Zone 2 Div...

Page 20: ...can also use documented switching actions for verification within the framework of regular proof test intervals The calculated values correspond to the values in the Characteristic Safety Values table...

Page 21: ...s not work Take appropriate measures to protect personnel and equipment while the safety function is not available Secure the application against accidental restart 3 Do not repair a defective device...

Page 22: ...safety function Probability of failure of components that are in the safety loop HFT Hardware Fault Tolerance MTBF Mean Time Between Failures MTTFD Mean Time To dangerous Failure MTTR Mean Time To Re...

Page 23: ...Functional Safety KFD2 SR2 Ex W LB Notes 2020 05 23...

Page 24: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 6656A...

Reviews: