Universal Transmitter Power Supply KF**-CRG2-(Ex)1.D
Editing Device Data: Current Output
7.5.1 Characteristic
With the parameters
Start value
and
End value
establish a sub-range of the input signal as the
measuring range of the application (section 7.5.3). This measuring range is formed linearly on the
output signal.
The following table shows, for the various characteristics (section 7.5), the conversion of the
Start value
and
End value
and the behaviour during measuring overrange.
• The statements apply for the setting
Inverted
Normal
.
• If you select
Inverted
Inverted
, the conversion of
Start value
and
End value
are reversed. The
start value is thus converted to 20 mA and the end value to 0 mA or 4 mA.
• Measuring overrange, which extend over the described linear range, cannot be evaluated. In the
case of such overrange, the specified value is constantly output.
Start value
——
End value
——
Inverted (7.5.1)
——
Inverted
Normal