![Pepperl+Fuchs HiD2024 Quick Start Manual Download Page 3](http://html1.mh-extra.com/html/pepperl-fuchs/hid2024/hid2024_quick-start-manual_1527907003.webp)
Rel
ea
se d
at
e
2
01
4-
09
-1
6
17
:0
3
D
at
e o
f i
ss
ue
20
14
-0
9-
16
18
59
30
_e
ng
.x
m
l
Technical data
HiD2024
3
Refer to "General Notes Relating to Fuchs Product Information".
Fuchs Group
USA: +1 330 486 0002
Singapore: +65 6779 9091
Germany: +49 621 776 2222
www.pepperl-fuchs.com
Switches 1 ... 4
Potentiometer 1 ... 4
The front-mounted potentiometers are used for fine adjustment of current transfer. The factory-setting of the device is calibrated
to the function transmitter power supply. If using the device as current driver, the Offset of the output stage can calibrated via the
potentiometers.
Configure the device in the following way:
• Push the red Quick Lok Bars on each side of the device in the upper position.
• Remove the device from Termination Board.
• Set the DIP switches according to the figure.
The device operates as a SMART transmitter power supply or as a repeater:
• As a SMART transmitter power supply, it provides a fully floating supply to power up to four 2-wire transmitters in a hazardous
area, repeating the current to drive a safe area source or sink mode output.
• As a repeater, it transmits a 4 mA ... 20 mA input signal from a control system to drive HART I/P converters, valve actuators,
and displays in a hazardous area.
Power
P
o
586
mW
Statement of conformity
PF 11 CERT 2109 X , observe statement of conformity
Group, category, type of protection,
temperature class
¬
II 3G Ex nA IIC T4 Gc
Electrical isolation
Input/Output
safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Input/power supply
safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Directive conformity
Directive 94/9/EC
EN 60079-0:2009, EN 60079-11:2007, EN60079-15:2005 , EN 60079-26:2007 , EN 61241-11:2006
General information
Supplementary information
EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.
The pins for this device are trimmed to polarize it according to its safety parameter. Do not change!
For further information see system description.
Configuration
CAUTION
Refer to the instruction
manual to install and
operate the unit
CH 1
ON
CH 2
ON
4
1
4
1
4
1
4
1
CH 3
ON
CH 4
ON
SWITCH SETTINGS
FUNCTION
for
EACH CHANNEL
Analog input with
source output 4-20mA
Analog input with
source output 1-5V
OFF
ON
OFF
ON
1
2
3
4
Analog input with
sink output 4-20mA
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
Analog output
ON
OFF
ON
OFF
Additional information