Technical data

HiD2024

3

Refer to "General Notes Relating to Fuchs Product Information".

Fuchs Group

USA: +1 330 486 0002

Singapore: +65 6779 9091

Germany: +49 621 776 2222

www.pepperl-fuchs.com

[email protected]

[email protected]

[email protected]

Switches 1 ... 4

Potentiometer 1 ... 4

The front-mounted potentiometers are used for fine adjustment of current transfer. The factory-setting of the device is calibrated 

to the function transmitter power supply. If using the device as current driver, the Offset of the output stage can calibrated via the 

potentiometers.

Configure the device in the following way:
• Push the red Quick Lok Bars on each side of the device in the upper position.

• Remove the device from Termination Board.

• Set the DIP switches according to the figure.

The device operates as a SMART transmitter power supply or as a repeater:
• As a SMART transmitter power supply, it provides a fully floating supply to power up to four 2-wire transmitters in a hazardous 

area, repeating the current to drive a safe area source or sink mode output.

• As a repeater, it transmits a 4 mA ... 20 mA input signal from a control system to drive HART I/P converters, valve actuators, 

and displays in a hazardous area.

Power

P

o

 586 

mW

Statement of conformity 

PF 11 CERT 2109 X , observe statement of conformity

Group, category, type of protection, 

temperature class 

¬

 II 3G Ex nA IIC T4 Gc

Electrical isolation 

 

Input/Output 

safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V

Input/power supply 

safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V

Directive conformity 

 

Directive 94/9/EC 

EN 60079-0:2009, EN 60079-11:2007, EN60079-15:2005 , EN 60079-26:2007 , EN 61241-11:2006

General information

Supplementary information 

EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of 

Conformity and instructions have to be observed where applicable. For information see www.pepperl-

fuchs.com.

The pins for this device are trimmed to polarize it according to its safety parameter. Do not change!

For further information see system description.

Configuration

CAUTION

Refer to the instruction
manual to install and 
operate the unit

CH 1

ON

CH 2

ON

4

1

4

1

4

1

4

1

CH 3

ON

CH 4

ON

SWITCH SETTINGS

FUNCTION

for

EACH CHANNEL

Analog input with
source output 4-20mA

Analog input with
source output 1-5V

OFF

ON

OFF

ON

1

2

3

4

Analog input with
sink output 4-20mA

OFF

OFF

ON

OFF

OFF

OFF

OFF

ON

Analog output

ON

OFF

ON

OFF

Additional information