FieldConnex® Basic Segment Coupler
Product Specifications
2
016-
04
9
PROFIBUS PA
Connection
3+, 6+, 2-, 5-, 1 shield, 4 shield
Rated voltage
24 ... 26 V
Rated current
max. 400 mA
Terminating impedance
100
, integrated
PROFIBUS DP
PROFIBUS with RS-485 transmission technology
Connection
terminals 7 RxD/TxD-P, 8 RxD/TxD-N, 9 shield, 10 FE
Baud rate
1.5 MBit/s max.
Indicators/operating means
Switch
PROFIBUS DP terminator
LED PWR
green: Power on
LED DP/ERR
red 2 Hz flashing: DP error red on: Hardware error red off:
DP communication detected
LED PA
red 2 Hz flashing: No PA communication or overload Off: PA
communication OK
Electrical isolation
PROFIBUS DP/PROFIBUS PA functional insulation acc. to IEC 62103, rated insulation
voltage 50 V AC /70 V DC
PROFIBUS DP/Supply
basic insulation according to IEC/EN 61010, rated insulation
voltage 253 V AC /357 V DC
PROFIBUS PA/Supply
basic insulation according to IEC/EN 61010, rated insulation
voltage 253 V AC /357 V DC
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU
EN 61326-1:2013
Standard conformity
Electromagnetic compatibility
NAMUR NE 21
Degree of protection
IEC/EN 60529
Fieldbus standard
EN 50170/2
Climatic conditions
DIN IEC 721
Shock resistance
EN 60068-2-27
Vibration resistance
EN 60068-2-6
Ambient conditions
Ambient temperature
-40 ... 60
°
C (-40 ... 140
°
F)
Storage temperature
-40 ... 85
°
C (-40 ... 185
°
F)
Relative humidity
< 95 % non-condensing
Shock resistance
15 g 11 ms
Vibration resistance
1 g 10 ... 150 Hz
Pollution degree
max. 2, according to IEC 60664
Corrosion resistance
acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection type
Terminals
Core cross-section
up to 2.5 mm
2
Technical Data