Fieldbus Valve Coupler FD0-VC-Ex4.FF
Error detection and problem solutions
40
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: G49 621 776-0 • USA +1 330 4253555 • Sin65 67799091 • Internet http://www.pepperl-fuchs.com
P
a
rt
N
o
.:
1
082
27
, D
a
te
o
f i
ssue
27
.0
3.2
006
7.3
Transducer block
Diagnosis messages
RS_STATE
Online
No error.
Failure
Hardware error.
Send device to Fuchs for
repair.
Stand-by
The target mode of the
block is OOS.
Set block into "Auto" mode.
Online Linking
One or several commu-
nication links to other
field devices are not
established.
• Check whether all necessary field de-
vices are available at the segment.
• Check configuration.
Problem
Elimination of error
Parameter
Message
Cause
Elimination
BLOCK_ERR
Block Configuration Error
The target mode is
"AUTO" or "MAN" and
the parameter "Actuator
Fail Action" is at "unde-
fined".
Parameterise the "Actuator
Fail Action" by entering the
drive mode "self-closing" or
"self-opening", see section
6.5.3.
Time monitoring or
Stroke Counter are ON
and "Sensor Usage" is at
"No Position Detection"
or "Use Sensor Values
for PV_D".
Set or automatically deter-
mine "Sensor Usage"
according to section 6.5.4 to
one of the options A ... D.
Time monitoring is ON
and one of the refer-
ence values for time
monitoring is at "0".
Enter reference values
according to section 6.5.6 or
determine them automati-
cally by means of starting
the setup wizard.
Input Failure
The status of the valve
position fed back to the
function block
(PRIMARY_ VALUE_D)
is "bad".
See "status values of pro-
cess parameters".
Output Failure
Combined error signal of
the errors displayed in
"XD_ERROR".
See „XD_ERROR“.
Maintenance Needed
The "Stroke Counter
Limit" has been
exceeded.
Drive and valve need main-
tenance since the stroke
number specified for this
case has been exceeded.
Then increase the "Stroke
Counter Limit" or reset the
counter value in the "Stroke
Counter".
Device Maintenance
Combined error signal of
the errors displayed in
"Valve Warning".
See "Valve Warning".
Problem
Elimination of error
Parameter
Message
Cause
Elimination