Trip Amplifier 2/208

Maintenance and Service

EN

5

Maintenance and Service

5.1

Maintenance

Only high-quality components are used. If you normal operate and pay attention to the 

installation remarks, no periodical maintenance is necessary. The long-term stability of 

these appliances means that an annual check of the zero point and the full scale value 

is sufficient. The relay´s life time must be observed (see technical data sheet).

5.2

Service information

If doubtful measuring results are achieved, the correct state of all external connecting 

parts and the output load must be checked. Make sure, that there is no overload. 

Check the fusible elements. The fuse is marked by its rated value and the covering 

sheet is also marked.
It is a fuse regulated in IEC 127-3, 250 V with the following rated value:
F1 = 400 mA, inert
When replacing components, always use new components of the same quality.
If there are any other faults, a laboratory standard test must be carried out. If reserve 

appliances are available, we recommend that the faulty appliance is given to our 

service department for inspection or for any repairs.

6

Safety  Concept

The appliances are developed on base of lots of safety rules. Hardware and software 

fulfil that catalogue of safety criterion. This trip amplifier is developed for standard 

applications. The sister-type 2/209 is available with TÜV certificate for safety 

applications in category SIL3 according to IEC 61508.
The configurable appliances have remarkable advantages in comparison to 

conventional trip amplifiers:

Continuous comparation of the analogue inputs with the reference values 

(conventional not possible).

Self-monitoring with dynamical dead man´s circuit) (conventional not possible).

Non-volatile EEPROM for data storage. Storage of operating system with EPROM 

(conventional not possible).

Check-back signal for relay status and continuous supervision of the coils as well 

as forced disconnection per watchdog (conventional not possible).

Simple RAM-test to check the store.

Lock against operations from outside (conventional not possible).

A fault switches into safe status.

CE declaration from manufacturer.

Technical changings possible.

536737.book  Seite 22  Montag, 1. Juni 2015  10:19 10

Summary of Contents for 2/208

Page 1: ...0102 ISO9001 2 208 TRIP AMPLIFIER GRENZWERTSCHALTER EN DE PROCESS AUTOMATION MANUAL HANDBUCH 536737 book Seite 1 Montag 1 Juni 2015 10 19 10...

Page 2: ...hnik und Elektroindustrie ZVEI e V in its most recent version as well as the supplementary clause Expanded reserva tion of proprietorship Es gelten die Allgemeinen Lieferbedingungen f r Erzeugnisse un...

Page 3: ...sipation 15 3 3 Connection of plug in units 16 3 4 Electromagnetic compatibility 17 3 5 Ground connection PE 17 4 Commissioning 18 4 1 Introduction 18 4 2 Checking the accuracy 18 4 3 Operation and tr...

Page 4: ...oltage rating 250V AC 250V DC Current rating 1 25 A AC DC Power rating 60 VA 30 W Mechanical life 20 mio operations Electrical life 0 5 mio operations Response time 20 ms variable Transistor max 30 V...

Page 5: ...perature of 60 C You can use the heat dissipation values shows in the table below to calculate the maximum number of appliances per switching cabinet in that case that you lay down 60 C as average tem...

Page 6: ...ection figures plug in unit The male connector is a consituent part of the trip amplifier the female connector fixed connector is to be installed in the 19 rack We recommend that fixed connectors are...

Page 7: ...st to twist unscreened wires 3 5 Ground connection PE The RFI Radio Frequency Interference immunity could be increased when connecting the PE The appliances functions are made sure even if the PE is n...

Page 8: ...ecified accuracy immediately or you have to wait for a certain time to warm up the appliance Usually the appliance works with an accuracy of 0 2 relating to the measuring range independent of the acci...

Page 9: ...ip point 1 G02 Trip point 2 Y01 Hysteresis Figure 3 Frontal sheet The frontal setting for trip point could be locked by an appliance internal jumper see section 4 4 figure 4 In that case the measuring...

Page 10: ...input signals Live Dead Zero Pay attention to the jumper setting as shown in figure 4 If status line indicates Y01 the hysteresis could be setted by the frontal keys The trip is on mid hysteresis Rela...

Page 11: ...he solder points to another solder jumper figure 4 Relay 1 Relay de energized high contact Relay 2 Relay de energized low contact Line monitoring On Input signals Live Zero 4 mA 20 mA 1 V 5 V 2 V 10 V...

Page 12: ...vailable we recommend that the faulty appliance is given to our service department for inspection or for any repairs 6 Safety Concept The appliances are developed on base of lots of safety rules Hardw...

Page 13: ...Trip Amplifier Grenzwertschalter 2 208 279938 2015 06 Pulscon LTC50 HART 536737 book Seite 23 Montag 1 Juni 2015 10 19 10...

Page 14: ...ION PROTECTING YOUR PROCESS Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check...

Reviews: