TRIP AMPLIFIER
GRENZWERTSCHALTER
EN
DE
PROCESS AUTOMATION
MANUAL/HANDBUCH
536737.book Seite 1 Montag, 1. Juni 2015 10:19 10
Page 1: ...0102 ISO9001 2 208 TRIP AMPLIFIER GRENZWERTSCHALTER EN DE PROCESS AUTOMATION MANUAL HANDBUCH 536737 book Seite 1 Montag 1 Juni 2015 10 19 10...
Page 2: ...hnik und Elektroindustrie ZVEI e V in its most recent version as well as the supplementary clause Expanded reserva tion of proprietorship Es gelten die Allgemeinen Lieferbedingungen f r Erzeugnisse un...
Page 3: ...sipation 15 3 3 Connection of plug in units 16 3 4 Electromagnetic compatibility 17 3 5 Ground connection PE 17 4 Commissioning 18 4 1 Introduction 18 4 2 Checking the accuracy 18 4 3 Operation and tr...
Page 4: ...oltage rating 250V AC 250V DC Current rating 1 25 A AC DC Power rating 60 VA 30 W Mechanical life 20 mio operations Electrical life 0 5 mio operations Response time 20 ms variable Transistor max 30 V...
Page 5: ...perature of 60 C You can use the heat dissipation values shows in the table below to calculate the maximum number of appliances per switching cabinet in that case that you lay down 60 C as average tem...
Page 6: ...ection figures plug in unit The male connector is a consituent part of the trip amplifier the female connector fixed connector is to be installed in the 19 rack We recommend that fixed connectors are...
Page 7: ...st to twist unscreened wires 3 5 Ground connection PE The RFI Radio Frequency Interference immunity could be increased when connecting the PE The appliances functions are made sure even if the PE is n...
Page 8: ...ecified accuracy immediately or you have to wait for a certain time to warm up the appliance Usually the appliance works with an accuracy of 0 2 relating to the measuring range independent of the acci...
Page 9: ...ip point 1 G02 Trip point 2 Y01 Hysteresis Figure 3 Frontal sheet The frontal setting for trip point could be locked by an appliance internal jumper see section 4 4 figure 4 In that case the measuring...
Page 10: ...input signals Live Dead Zero Pay attention to the jumper setting as shown in figure 4 If status line indicates Y01 the hysteresis could be setted by the frontal keys The trip is on mid hysteresis Rela...
Page 11: ...he solder points to another solder jumper figure 4 Relay 1 Relay de energized high contact Relay 2 Relay de energized low contact Line monitoring On Input signals Live Zero 4 mA 20 mA 1 V 5 V 2 V 10 V...
Page 12: ...vailable we recommend that the faulty appliance is given to our service department for inspection or for any repairs 6 Safety Concept The appliances are developed on base of lots of safety rules Hardw...
Page 13: ...Trip Amplifier Grenzwertschalter 2 208 279938 2015 06 Pulscon LTC50 HART 536737 book Seite 23 Montag 1 Juni 2015 10 19 10...
Page 14: ...ION PROTECTING YOUR PROCESS Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check...