Pentair T43 Instruction Manual Download Page 1

© 2014 Pentair Equipment Protection

89056284

Rev. F

P/N 10-1008-145

T-SERIES

Air Conditioner

t43 Model

INSTRUCTION MANUAL

Summary of Contents for T43

Page 1: ... 2014 Pentair Equipment Protection 89056284 Rev F P N 10 1008 145 T SERIES Air Conditioner T43 Model INSTRUCTION MANUAL ...

Page 2: ...NSIONAL DRAWINGS 4 MOUNTING CUTOUT DIMENSIONS 5 MOUNTING GASKET KIT 6 Components List 7 Wiring Diagram and Schematic 8 Generic Wire Diagram actual unit options may vary 8 Generic Schematic actual unit options may vary 9 TEMPERATURE CONTROL 10 Units With Heat 10 PRINCIPLES OF OPERATION 10 MAINTENANCE 10 Compressor 10 Inlet Air Filter 10 How To Remove Clean or Install a New Inlet Air Filter 11 Conde...

Page 3: ...ITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate ...

Page 4: ... exit point of the air conditioner The drain tube must be on a continuous downward slope A slight elevation of the tube could result in secondary trap FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN 6 Refer to top of nameplate for electrical requirements Connect the power cord to a properly grounded power supply Use of an extension cord is not recommend...

Page 5: ... 2014 Pentair Equipment Protection 89056284 5 8 10K BTU MOUNTING CUTOUT DIMENSIONS External Cutout Internal Cutout ...

Page 6: ... 2014 Pentair Equipment Protection 89056284 6 MOUNTING GASKET KIT ...

Page 7: ... 6000 BTU 8000 BTU 10000 BTU 10000 BTU Capacitor CompressNor Start 10 1032 14 10 1032 08 10 1032 08 N A Capacitor Compressor Run S 6173 S 6173 52 6032 01 N A Capacitor Impeller Condenser 52 6084 02 52 6084 02 52 6084 05 52 6032 20 Capacitor Impeller Evaporator 52 6084 02 52 6084 02 52 6084 02 52 6032 44 Coil Condenser 45 6051 00 45 6051 00 45 6051 00 45 6051 00 Coil Evaporator 43 6025 00 45 6050 0...

Page 8: ... F H D76 K7 4 E7DH 57 5AD6 4 4D I F 4 G 9D 9D K7 F 7D AEF3F 8D77L7 BD7EEGD7 5A FDA B7 7D 3 4 7 F 40 7 9 6 9D 40 4 3 8 7 4 EI F5 56 46 2 4 4 56 46 AD9 I F K7 H 86 H 86 5 5AA 9 F 7D AEF3F 73F 9 F 7D AEF3F K7 4 4 4D 4 4D 2 470 4D H 86 H 86 4 I F I F I F 4 G F EI F5 7E 3GFA E 3 4 5 I F I F I F 4 G 4 4 4 4 I F 4 G 4 H 86 H 86 470 2 4 7 40 9D 7 5 AEGD7 B7 7D 4D 40 7 4 4 H I F H 4 4 G ABB EGBB AD 8800609...

Page 9: ... 2014 Pentair Equipment Protection 89056284 9 GENERIC SCHEMATIC FOR 1 PHASE MODELS ACTUAL UNIT OPTIONS MAY VARY GENERIC WIRE DIAGRAM FOR 3 PHASE MODELS ACTUAL UNIT OPTIONS MAY VARY ...

Page 10: ...sor are provided for recharging and or checking suction and discharge pressures Under no circumstances should the access fitting covers be loosened removed or tampered with Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for rec...

Page 11: ...lter do so from both sides for maximum concentration of adhesive CONDENSER AND EVAPORATOR AIR MOVERS Impeller motors require no maintenance All bearings shafts etc are lubricated during manufacturing for the life of the motor If the condenser impeller motor ambient impeller should fail it is not necessary to remove the air conditioner from the cabinet or enclosure to replace the blower The condens...

Page 12: ...rflow Is there airflow YES proceed to step 6 NO possible problem Defective thermostat Open motor winding Stuck impeller motor Obstructed wheel Repair or Replace defective part 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm Is the compressor showing signs of this YES wait 5 minutes then proceed to step 7 NO poss...

Page 13: ...t but won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Undersized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in Mounting gasket damaged For additional technical support i e amp draw...

Page 14: ...ir Equipment Protection label affixed to product without written Pentair Equipment Protection approval Pentair Equipment Protection must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself...

Page 15: ...is fee If approval is not received within 30 days material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer E At Buyer s request Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 150 per hour Engineering charge plus any other incurred testin...

Page 16: ... 2014 Pentair Equipment Protection 89056284 Rev F P N 10 1008 145 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairProtect com ...