© 2014 Pentair Equipment Protection
89104461
- 16 -
HOW TO REMOVE, CLEAN OR INSTALL A NEW INLET AIR FILTER
RP aluminum washable air filters are designed to provide excellent filtering efficiency with a high dust holding
capacity and a minimum amount of resistance to air flow. Since they are constructed entirely of aluminum,
they are lightweight and easy to service. Optimum filter performance is maintained by recoating the filters
after washing with RP Super Filter Coat adhesive. To achieve maximum performance from your air handling
equipment, air filters should be cleaned on a regular basis.
The inlet air filter is located behind the right side panel. To access the filter, pull from slot on top cover. The filter
may now be cleaned or a new filter installed.
Cleaning Instructions:
1. Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS.
2. After flushing, allow filter to drain. Placing it with a corner down will assure complete drainage.
3. Recoat the filters with RP Super Filter Coat adhesive. When spraying filter do so from both sides
for maximum concentration of adhesive.
CONDENSER AND EVAPORATOR AIR MOVERS
Blower motor requires no maintenance. All bearings, shafts, etc. are lubricated for the life of the motor during
manufacturing.
If one of the condenser impeller motors (ambient impellers) should fail, it is not necessary to remove the air
conditioner from the cabinet or enclosure to replace the blower. The condenser blower is mounted on its own
bulkhead and is easily accessible by removing the front cover.
Operation of the air conditioner in areas containing airborne
caustics or chemicals can rapidly deteriorate filters, condenser
coils, blowers and motors, etc. Contact Pentair Equipment
Protection for special recommendations.
CAUTION
REFRIGERANT LOSS
Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks. Shipping
damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during
manufacture may require repair or recharging of the system. This work should only be performed by qualified
professionals, generally available through a local, reputable air conditioning repair or service company.
Refer to the data on the nameplate which specifies the type of refrigerant and the charge size in ounces.
Before recharging, make sure there are no leaks and that the system has been properly evacuated into a deep
vacuum.
Summary of Contents for ProAir CR29
Page 11: ... 2014 Pentair Equipment Protection 89104461 11 WIRE DIAGRAM LEVEL II AND III 2000 BTU ...
Page 12: ... 2014 Pentair Equipment Protection 89104461 12 SCHEMATIC LEVEL II AND III 2000 BTU ...
Page 17: ... 2014 Pentair Equipment Protection 89104461 17 NOTES ...
Page 20: ... 2014 Pentair Equipment Protection 89104461 20 NOTES ...
Page 21: ... 2014 Pentair Equipment Protection 89104461 21 NOTES ...