Parameter
Unit of Measure
Value
Description
Default
Min.
Max.
Upper Pressure Setting (UPS)
psi
50
10
90
Sets the pressure for when the pump stops
running. Traditionally the Cut-Out setting.
Lower Pressure Setting (LPS)
psi
30
0
UPS - 1
Sets the pressure for when the pump starts
running. Traditionally the Cut-In setting.
Over Pressure
psi
80
UPS + 5
100
Sets Over Pressure Fault value.
Service Factor Amps
A
-
0
12
Service factor amps (max. load) of motor the
device is operating.
Extended Run Time
Minutes
60
1
65000
Number of minutes device can run before it
faults on Extended Runtime.
Dry Run
-
Enabled
Disabled
Enabled
Enables or disables Dry Run Detection.
Dry Run Delay
Minutes
1
65000
Time device waits to restart pump when Dry
Run is detected.
Dry Run Detection Time
Seconds
30
1
65000
Time the device takes to recognize Dry Run
condition.
Pressure
psi
-
0
100
Displays the actual system pressure at the
point of last data retrieval.
PARAMETER LIST
Figure 3: System Settings
Online Device Registration
1. Download the App to your mobile device from Apple App
Store® or Google Play®.
2. Open the App.
Existing users: Login to your account, click DEVICES
and then ADD NEW DEVICE.
New users: Scroll down in the app and click SIGN UP AS
A CUSTOMER.
3. Follow prompts to enter device and system information.
Complete online device registration.
The Pentek Well Defender’s unique device ID code is
required for this step and can be found on the inner
cover of the device itself.
DEVICE DETAILS
PUMP START PRESSURE (CUT-
IN)
AUTO RESET DELAY (HH:MM)
DRY RUN SENSITIVITY
ON
ON
PUMP STOP PRESSURE (CUT-
OUT)
PRESSURE SETTINGS
DRY RUN
Update Value
Enter whole number between (Cut-In
+5) and 95
Submit
Cancel
50
30 PSI
50 PSI
INSTALLATION
7
PN1053 (06-10-20)