© 2015 Pentair Equipment Protection
89117329
- 9 -
2000 BTU/HR. UNIT CHARACTERISTICS
Model
N170216GXXX
N170226GXXX
N170246GXXX
Dimensional Data
Height (in./mm)
18.0 / 458
18.0 / 458
22.5 / 572
Width (in./mm)
12.0 / 305
Depth (in./mm)
8.40/215
Unit Weight (lb./kg)
54/25
54/25
73/33
Unit Protection Rating
Type 12
Cooling Data
Refrigerant
R134a
Refrigerant Charge
5.5 oz.
5.4 oz.
5.4 oz.
Cooling Capacity at 95 F Enclosure
95 F Ambient (BTU/Hr.)
1460 / 1820
1410 / 1720
1410 / 1720
Cooling Capacity at Max Conditions
(BTU/Hr.)
1500/1800
1450/1650
1450/1650
Maximum Ambient Temp
125 F/52 C
Minimum Ambient Temp
50 F/10 C
Enclosure Airflow
59/70 CFM
External Airflow
97/117 CFM
Condensate Management
Hose discharge/C/E
Electrical Data
Rated Voltage (50/60 Hz)
110/115 V
220/230 V
400/460 V
Rated Frequency
50/60 Hz
Voltage Range
+/- 10% of rated
Cooling Amps at Max Conditions
7.2 / 7.1
3.1 / 3.1
1.6 / 1.6
Compressor RLA/LRA
4.9 / 27.5
2.5 / 13
2.5 / 13
Evaporator Fan RLA
.30/.28
.15/.15
.15/.15
Condenser Fan RLA
.30/.28
.15/.15
.15/.15