SPECTRACOOL™

Air Conditioner

n17 Model

INSTRUCTION MANUAL

Summary of Contents for N17

Page 1: ... 2015 Pentair Equipment Protection 89117329 Rev G P N 89117329 SPECTRACOOL Air Conditioner N17 Model INSTRUCTION MANUAL ...

Page 2: ...ay vary 11 1000 BTU Hr 115V 230V Generic Wire Diagram actual unit options may vary 12 2000 BTU Hr 115V 230V Generic Wire Diagram actual unit options may vary 13 2000 BTU Hr 115V 230V Generic Schematic actual unit options may vary 14 1000 BTU Hr 460V Generic Wire Diagram actual unit options may vary 15 1000 BTU Hr 460V Generic Schematic actual unit options may vary 16 2000 BTU Hr 460V Generic Wire ...

Page 3: ...r conductors only Power supply wiring should be restrained after field installation to ensure no contact with internal fan Minimum circuit ampacity should be at least 125 of the amperage shown on the unit nameplate No other equipment should be connected to this circuit to prevent overloading Immediately after applying power the evaporator blower enclosure air should start running Operate the air c...

Page 4: ...right for a minimum of five 5 minutes before starting CAUTION Air conditioner must be in upright position during operation 5 Refer to the nameplate for electrical requirements Wire the unit to a properly grounded power supply Electrical circuit to include either a slow blow fuse or an HACR circuit breaker 6 Some air conditioners require a remote mounted thermostat Wire the thermostat outputs to th...

Page 5: ... 2015 Pentair Equipment Protection 89117329 5 287 1 89089862 Surface Mount Figure 1 Cutout Drawing ...

Page 6: ...ontinuously this can only mean that ambient air is entering the enclosure Be aware that frequent opening of the enclosure s door admits humid air that the air conditioner must then dehumidify STANDARD AND OPTIONAL COMPONENT OPERATION THERMOSTAT The thermostat setpoint equals the temperature that the air conditioner turns off The thermostat has a 10 F differential from setpoint until it calls for c...

Page 7: ...1 7 6 8 75 23 9 78 20 28 9 4 80 26 7 86 7 15 26 1 0 85 29 4 95 10 23 3 2 90 32 2 105 5 20 6 4 95 35 113 3 0 17 8 7 5 100 37 8 125 5 15 9 105 40 6 135 10 12 2 12 110 43 3 146 7 15 9 4 15 115 46 1 157 5 20 6 7 18 5 120 48 9 170 25 3 9 22 125 51 7 185 30 1 1 26 130 54 4 197 5 35 1 7 30 135 57 2 213 3 40 4 4 35 140 60 230 45 7 2 40 145 62 8 246 7 50 10 45 5 150 65 6 263 8 55 12 8 51 5 ...

Page 8: ...Enclosure 95 F Ambient BTU Hr 900 1110 1100 1290 1100 1290 Cooling Capacity at Max Conditions BTU Hr 1150 1400 1100 1300 1100 1300 Maximum Ambient Temp 125 F 52 C Minimum Ambient Temp 50 F 10 C Enclosure Airflow 59 70 CFM External Airflow 97 117 CFM Condensate Management Hose discharge C E Electrical Data Rated Voltage 50 60 Hz 110 115 V 220 230 V 400 460 V Rated Frequency 50 60 Hz Voltage Range 1...

Page 9: ...F Enclosure 95 F Ambient BTU Hr 1460 1820 1410 1720 1410 1720 Cooling Capacity at Max Conditions BTU Hr 1500 1800 1450 1650 1450 1650 Maximum Ambient Temp 125 F 52 C Minimum Ambient Temp 50 F 10 C Enclosure Airflow 59 70 CFM External Airflow 97 117 CFM Condensate Management Hose discharge C E Electrical Data Rated Voltage 50 60 Hz 110 115 V 220 230 V 400 460 V Rated Frequency 50 60 Hz Voltage Rang...

Page 10: ...7 8 20 5 10 80 100 3 1 3 7 11 23 5 10 N170126GXXX 65 80 1 7 2 2 11 25 10 21 80 100 1 8 2 3 13 27 11 22 N170146GXXX 65 80 0 9 1 1 11 25 10 21 80 100 0 9 1 2 13 27 11 22 N170216GXXX 65 80 4 3 5 6 11 26 9 20 80 100 4 4 5 8 14 31 11 25 N170226GXXX 65 80 2 1 2 6 15 27 8 20 80 100 2 2 2 9 15 33 5 20 N170246GXXX 65 80 1 1 1 3 15 27 8 20 80 100 1 1 1 5 15 33 5 20 ...

Page 11: ... 2015 Pentair Equipment Protection 89117329 11 WIRE DIAGRAMS AND SCHEMATICS 1000 BTU HR 115V 230V GENERIC WIRE DIAGRAM ACTUAL UNIT OPTIONS MAY VARY ...

Page 12: ... 2015 Pentair Equipment Protection 89117329 12 1000 BTU HR 115V 230V GENERIC WIRE DIAGRAM ACTUAL UNIT OPTIONS MAY VARY ...

Page 13: ... 2015 Pentair Equipment Protection 89117329 13 2000 BTU HR 115V 230V GENERIC WIRE DIAGRAM ACTUAL UNIT OPTIONS MAY VARY ...

Page 14: ... 2015 Pentair Equipment Protection 89117329 14 2000 BTU HR 115V 230V GENERIC SCHEMATIC ACTUAL UNIT OPTIONS MAY VARY ...

Page 15: ... 2015 Pentair Equipment Protection 89117329 15 1000 BTU HR 460V GENERIC WIRE DIAGRAM ACTUAL UNIT OPTIONS MAY VARY ...

Page 16: ... 2015 Pentair Equipment Protection 89117329 16 1000 BTU HR 460V GENERIC SCHEMATIC ACTUAL UNIT OPTIONS MAY VARY ...

Page 17: ... 2015 Pentair Equipment Protection 89117329 17 2000 BTU HR 460V GENERIC WIRE DIAGRAM ACTUAL UNIT OPTIONS MAY VARY ...

Page 18: ... 2015 Pentair Equipment Protection 89117329 18 2000 BTU HR 460V GENERIC SCHEMATIC ACTUAL UNIT OPTIONS MAY VARY ...

Page 19: ...9117326SP 89117326SP Thermostat SPDT 55100F 10106116SP 10106116SP 10106116SP Transformer Input Power NA NA 101006149SP 2000 BTU HR COMPONENTS LIST Part Description Part Number 115 V 1 Phase 230 V 1 Phase 460 V 1 Phase Capacitor Compressor Start 89111993SP 89117017SP 89117017SP Coil Condenser 89088819SP 89088819SP 89088819SP Coil Evaporator 17100201SP 17100201SP 17100201SP Compressor 89108747SP 891...

Page 20: ...rating temperature increases above designed conditions due to a dirty or clogged filter or plugged condenser coil the air conditioner s compressor will stop operating due to actuation of the thermal overload cut out switch located on the compressor housing As soon as the compressor temperature has dropped to within the switch s cut in setting the compressor will restart automatically However the a...

Page 21: ...rigeration leaks Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacture may require repair or recharging of the system This work should only be performed by qualified professionals generally available through a local reputable air conditioning repair or service company Should the refrigerant charge be lost access ports on th...

Page 22: ...n for airflow Is there airflow YES proceed to step 6 NO possible problem Defective thermostat Open motor winding Stuck fan motor Obstructed blades Repair or Replace defective part 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm Is the compressor showing signs of this YES wait 5 minutes then proceed to step 7 NO ...

Page 23: ... Compressor tries to start but won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad overload switch Bad start capacitor Unit blows breakers Undersized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in Mounting gasket damaged For additional technical support conta...

Page 24: ... 2015 Pentair Equipment Protection 89117329 24 NOTES ...

Page 25: ... 2015 Pentair Equipment Protection 89117329 25 NOTES ...

Page 26: ...ir Equipment Protection label affixed to product without written Pentair Equipment Protection approval Pentair Equipment Protection must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself...

Page 27: ...is fee If approval is not received within 30 days material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer E At Buyer s request Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 150 per hour Engineering charge plus any other incurred testin...

Page 28: ... 2015 Pentair Equipment Protection 89117329 Rev G P N 89117329 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairProtect com ...