Pentair MYERS K4563 Installation And Service Manual Download Page 7

K4563  11/08/12

7

  12.  Motor  winding  re sis tance  read ings.

     a.  Disconnect all three motor leads from panel  

 

terminal blocks.

     b.  Using a volt-ohmmeter, with the scale set on  

 

RX1, measure the resistance be tween the  

 

leads with the chart.

Winding

Resistance Reading

Main

Lowest

Start

Next

Lowest

(Middle)

Both

Highest

(Main & Start)

  13.  Capacitor  check.

 

a.  Make sure the ca pac i tor is dis charged. Use 

extreme caution as a spark might occur.

 

b.  Disconnect the ca pac i tor leads and connect 

an analog-type volt-ohmmeter to the 

capacitor terminals.

 

c.  Set the meter on the RX1,000 scale to check 

the start ca pac i tor. Set the meter on the 

RX10,000 scale to check the run ca pac i tor.

 

d.  The meter should in di cate low ohms when it is 

first connected, but as the ca pac i tor becomes 

charged (by the meter), it will return to a 

reading of infinity (open circuit).

  14.  Start relay check.

     a.  Check the coil re sis tance. It should be 3,000  

 

to 15,000 ohms.

     b.  Install a clamp on amp meter around the start  

 

wind ing  lead.

     c.  Set the amp meter scale to at least 2 times  

 

the pump motor full load current.

     d.  Place the H-O-A switch in the Hand position  

 

to start the pump.

     e.  The meter should read ap prox i mate ly 2 times  

 

full load current during starting. 

     f.  After the motor has started (within one    

 

second) the cur rent should drop to a value  

 

much less than full load cur rent.

  15.  Motor voltage check:

Component

Mode

Voltage

Reading

Main Winding

Start

Line Voltage

Main Winding

Run

Line Voltage

Start Winding

Start

Line Voltage

Start Winding

Run

120%

Line Voltage

Summary of Contents for MYERS K4563

Page 1: ...make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system STANDARD ELECTRICAL CONTROLS INSTALLATION AND SERVICE MANUAL Part K4563 2012 Pent...

Page 2: ...get metal chips in the components while cutting hole After the hole is cut any metal particles must be removed from the box Failure to do so may result in premature component failure Connect incoming...

Page 3: ...sure H O A switch is left in the Auto position after start up is completed Pump Start Up Refer to pump Installation and Service Manual PUMP MAINTENANCE WARNING Before handling these pumps and controls...

Page 4: ...the HIGH WATER and the LAG OVERRIDE float position should be reversed SEAL FAILURE INPUTS Your pump may be equipped with a seal fail moisture sensor Refer to your pump owner s manual to determine if...

Page 5: ...ugh to ac ti vate the floats 4 If there is enough water in the system with the power turned off mark and disconnect the off and on floats Next install jumper wires in the terminal blocks for off and o...

Page 6: ...or solids 3 Possible motor failure fault in windings 4 Pump may be miswired to terminal block 5 Voltage and current unbalance Three phase only Voltage unbal ance on three phase power sources can cause...

Page 7: ...i tor d The meter should in di cate low ohms when it is first connected but as the ca pac i tor becomes charged by the meter it will return to a reading of infinity open circuit 14 Start relay check a...

Page 8: ...ions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal...

Reviews: