23833A470  02/26/13

3

pump castings are made of ASTM A-48 Class 30 cast 

iron.  The wear ring is bronze and all impellers are 

two vane enclosed solids handling design made from 

ductile iron.

General Installation: 

 Various configurations 

and methods of plumbing this series of solids 

handling pumps may be used; however, for ease of 

installation and service a Myers rail lift-out system is 

recommended.

Note:

  If the hazardous location pumps are used in 

conjunction with a rail lift-out system, it must be a 

Factory Mutual approved nonsparking, hazardous 

location system.  The Myers approved lift-out  

models are:

4" Lift-out

8" Lift-out

12" Lift-out

SRAX44HH

SRAX88

SRAX1212

If these Guidelines are not followed, the Factory 

Mutual Hazardous Location approval is void.

Hazardous Location Service:

  These pumps are to 

be used for handling sewage, wastewater and storm 

water only.  

Do not

 use in other hazardous locations.  

These pumps must be repaired and serviced only at 

Myers Authorized Service Centers or at the Myers 

factory.  Any unauthorized field repair voids warranty 

and the hazardous location rating.

CAUTION:  After the pump is installed and sewage 

has entered the basin there are methane and 

hydrogen sulfide gases, which are poisonous.  

Never enter a wet well unless the cover is open 

for a sufficient period of time to allow fresh air 

into the basin.  It is for this reason that  Myers 

recommends using the rail lift-out system so that 

no service is required inside the basin.

Motor: 

 Each motor is provided with heat sensor 

thermostats attached directly to the motor windings.  

The thermostats open if the motor windings see 

excessive heat and, in turn, open the motor contractor 

in the control panel, breaking the power to the pump.  

When the motor is stopped due to an overheated 

condition, it will not start until the motor has cooled 

and the heat sensor reset button is manually pushed.  

This circuitry is provided in the Myers control panel 

designs.

The thermostats are set to open at a temperature of 

302°F (150°C).  The maximum contact rating is 18 

amps at 115 VAC and 12 amps at 230 VAC.

Note:

  Failure to use proper circuitry and to connect 

the motor overheat protection in the control panel 

would negate all warranties and Factory Mutual 

approval.

Motor Seal Failure Warning: 

 The seal chamber is 

oil filled and provided with moisture sensing probes 

to detect water leakage through the lower shaft seal.  

The probes can also detect moisture present in the 

upper motor housing.

The presence of water energizes a red seal leak 

warning light at the control panel.  This is a 

warning 

light only

, and does not stop the motor.  It indicates 

a leak has occurred and the pump must be repaired.  

Normally, this indicates the outboard seal has leaked.  

Allowing the unit to operate after the warning could 

cause upper seal leakage along with motor failure.

The resistance across the moisture sensing (seal 

failure) probes should be checked after a seal 

leak warning light has lit.  This can be done by 

disconnecting the red and orange control wires from 

the control panel and measuring the resistance with 

an ohmmeter between the wires.  If the measured 

values are below specification, then the pump may 

have a lower seal failure and require service.

On the Myers hazardous location control panels 

the seal leak test switch tests the seal leak circuit 

continuity.  When pushed the seal leak test bulb 

should light.  If the test bulb does not light it means 

either the wiring circuitry to the seal leak probes has 

been broken or the bulb has burned out.

Note:

  Myers built control panels supply the correct 

circuitry for moisture and heat sensor connections.  

Failure to install the correct circuitry with proper 

connection would negate warranty and Factory 

Mutual approval.  

Motor Power Cord, Control Cord and Cord Cap 

Assembly:

  Each motor power cord has 4 conductors: 

white, black, red and green.  For a three phase motor 

the red, black and white conductors connect to the 

three line leads, and the green is connected to a good 

ground.  Interchanging any two line leads will reverse 

the rotation of the motor.

Note:

  Rotation should be clockwise when observed 

from the top of the pump.  This can be checked by 

noting which direction the pump torque is up on 

initial starting.  A properly rotating pump will torque 

counterclockwise upon start.

The control cable has 5 conductors: black, white, 

red, orange and green.  White and black connect to 

the heat sensor terminals in the control panels; red 

and orange connect to the seal failure terminals in the 

control panel; and the green connects to the ground in 

the control panel.

The cord cap is epoxy potted.  The cord cap provides 

for a sealed wire connection with terminals so that 

connections can be made without breaking the motor 

seal.  A hazardous location junction box is required for 

Summary of Contents for Myers 12VL

Page 1: ...he equip ment or to the responsible party who maintains the system MODELS 4VL X 8SM X 8VL X and 12VL X Used in Hazardous Locations Class I Division 1 SUBMERSIBLE SOLIDS HANDLING PUMPS INSTALLATION AND...

Page 2: ...or maximum performance as this could cause the motor to overheat 18 Secure the pump in its operating position so it cannot tip over fall or slide 19 Keep hands and feet away from impeller when power i...

Page 3: ...lled and provided with moisture sensing probes to detect water leakage through the lower shaft seal The probes can also detect moisture present in the upper motor housing The presence of water energiz...

Page 4: ...isassembly and reassembly process WARNING Disconnect pump from power source before servicing or handling pump DISASSEMBLY 1 With the pump located in a secure place remove the bolts fastening the seal...

Page 5: ...peller onto the shaft making sure that the seal spring is registered properly onto the back side of the impeller Insert the bolt and washer assembly into the shaft and tighten to 193 ft lbs Replace th...

Page 6: ...n for checking 2 Trouble may be from clogged impeller causing motor to overload or could be from failed motor 3 Trouble may be from faulty component in control box Always check control box before remo...

Page 7: ...operate erratically CAP SCREW TORQUE VALUE 3 8 16 20 ft lbs 1 2 13 43 ft lbs 5 8 11 93 ft lbs 3 4 10 128 ft lbs 7 8 14 193 ft lbs 1 7 2 8 3 9 4 5 6 1 7 2 8 3 9 4 5 6 1 2 3 POTTING RESIN CONTROL CORD T...

Page 8: ...23833A470 02 26 13 8 4VL 4VLX AND 8SM 8SMX PUMPS 14 11 12 13 9 10 15 16 17 18 19 20 21 22 23 24 25 27 30 31 33 34 40 29 32 35 36 39 38 37 44 43 47 46 45 26 42 41 28 1 2 3 4 5 6 7 8...

Page 9: ...0 D 1 See Chart See Chart 33 O RING 7 1 2 x 7 1 4 x 1 8 1 05876A127 05876A127 34 PLATE SEAL 1 25261D000 25261D000 35 WASHER IMPELLER RETAINER 1 1945 001 3 1945 001 3 36 CAP SCREW SOCKET HD 1 3879 002...

Page 10: ...3833A470 02 26 13 10 37 52 51 50 49 45 46 1 2 3 4 5 6 7 9 8 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 32 31 33 34 35 36 40 39 38 41 42 43 44 47 48 53 8VL 8VLX AND 12VL 12VLX PUMPS...

Page 11: ...T 2 25449A000 25449A000 26 RING RETAINING 1 12558A031 12558A031 27 PLUG 3 8 NPT PIPE 3 05022A062 05022A062 28 SEAL LABYRINTH 1 25262C000 25262C000 29 CAP SCREW HEX HD 1 2 13 x 2 1 4 24 19103A049 19103...

Page 12: ...M4 53 8VLX750M4 53 25447D010 25444D016 8VL1000M4 43 8VLX1000M4 43 25447D010 25444D010 8VL1000M4 53 8VLX1000M4 53 25447D010 25444D011 8VL1250M4 43 8VLX1250M4 43 25447D010 25444D010 8VL1250M4 53 8VLX125...

Page 13: ...inute Total Head M F 60 50 40 30 20 10 200 180 160 140 120 100 80 60 40 20 1750 RPM 1150 RPM 870 RPM 1150 RPM 870 RPM Total Head in Feet 100 90 80 70 60 50 40 30 20 10 PERFORMANCE CURVE DIMENSIONS DIM...

Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 15: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 16: ...failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services...

Reviews: