background image

   

10-1008-62 rev 10 

 

TEMPERATURE CONTROL 

 
The electromechanical thermostat is factory preset to 75°F/23°C. To change the temperature setting, 
remove the nylon plug from the back face of the unit. Use a standard screwdriver to adjust thermostat. 
For cooler temperatures turn clockwise, for warmer temperatures turn counterclockwise. 
 
 

PRINCIPLES OF OPERATION 

 
If electrical power to the air conditioner is interrupted and reapplied immediately, (within 3 to 5 seconds), 
the compressor may not restart due to the high back pressure of the compressor. It takes a minimum of 
one (1) minute after shutdown for the compressor suction and discharge pressures to equalize in order 
for the air conditioner to restart. 
 
Operating the air conditioner below the minimum ambient temperature or above the maximum ambient 
temperatures indicated on the nameplate voids all warranties. 
 
It is recommended that the warranty section of this manual be read in order to familiarize yourself with 
parameters of restricted operation. 
 
The moisture that the enclosure air can contain is limited. If moisture flows from the drain tube 
continuously this can only mean that ambient air is entering the enclosure. Be aware that frequent 
opening of the enclosure’s door admits humid air that the air conditioner must then dehumidify. 
 
 

MAINTENANCE  

 
Compressor

 

The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and 
should provide years of satisfactory operating service. 
 
Should the refrigerant charge be lost, recharging ports (access fittings) on the suction and discharge 
sides of the compressor are provided for recharging and/or checking suction and discharge pressures. 
 
Under no circumstances should the access fitting covers be loosened, removed or tampered with. 
 
Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic 
system. 
 
Recharging ports are provided for the ease and convenience of reputable refrigeration repair service 
personnel for recharging the air conditioner. 
 

Inlet Air Filter 

Proper maintenance of the inlet air filter, located behind the front grille, will assure normal operation of the 
air conditioner. If filter maintenance is delayed or ignored, the maximum ambient temperatures under 
which the unit is designed to operate will be decreased. 
 
If the compressor’s operating temperature increases above designed conditions due to a dirty or clogged 
filter (or plugged condenser coil), the air conditioner’s compressor will stop operating due to actuation of 
the thermal overload cutout switch located on the compressor housing. As soon as the compressor 
temperature has dropped to wit

hin the switch’s cut-in setting, the compressor will restart automatically. 

However the above condition will continue to take place until the filter has been cleaned or replaced. 
  
 
317-257-6811                                

WWW.McLeanParts.net

                             317-257-1590 fax 

Summary of Contents for McLean THERMAL RCR11 Series

Page 1: ...1 10 1008 62 rev 10 MAI Prime Parts 5736 N Michigan Road Indianapolis IN 46228 Tel 317 257 6811 Fax 317 257 1590 W W W M C L E A N P A R T S N E T INSTRUCTION MANUAL FOR RCR11 AIR CONDITIONER ...

Page 2: ...en file a claim with the delivering carrier McLean Thermal cannot accept responsibility for freight damages however we will assist you in any way possible HANDLING TESTING THE AIR CONDITIONER If it is necessary to place the air conditioner in a horizontal position after unpacking be certain it is placed in an upright vertical or mounting position for a minimum of five 5 minutes before operating Ne...

Page 3: ...ll restart after it has cooled to within the thermal overload cut in temperature setting INSTALLATION Step 1 Inspect air conditioner Verify functionality before mounting the air conditioner see Handling Testing the Air Conditioner on page 1 Step 2 Determine if the unit is to be surface or recess mounted Using the appropriate cutout dimensions shown on page 5 of this manual prepare the enclosure op...

Page 4: ...115 50 60 9 0 9 0 1 1800 2000 131 55 95 lbs RCR11 0226 GXXX 230 50 60 5 1 4 7 1 1800 2000 131 55 95 lbs RCR11 0416 GXXX 115 50 60 12 9 12 9 1 3800 4000 131 55 105 lbs RCR11 0426 GXXX 230 50 60 7 1 7 1 1 3800 4000 131 55 105 lbs XXX will be replaced with a three digit number designating all desired options Consult the factory for specific model numbers RCR11 Model Drawing 317 257 6811 WWW McLeanPar...

Page 5: ... 00 11 1002 00 11 1002 00 11 1002 00 Compressor AE AK 10 1016 22 10 1016 26 10 1026 74 10 1026 77 Condenser Discharge Duct 11 6037 00 11 6037 00 11 6037 00 11 6037 00 Filter Air Reusable 10 1000 12 10 1000 12 10 1000 12 10 1000 12 Filter Dryer 52 6028 00 52 6028 00 52 6028 00 52 6028 00 Relay Compressor Start 10 1028 05 10 1028 14 10 1028 07 10 1028 15 Service Cord 52 6035 01 52 6035 0 52 6035 74 ...

Page 6: ...5 10 1008 62 rev 10 RCR11 Wire Diagram 4000 BTU UNIT 317 257 6811 WWW McLeanParts net 317 257 1590 fax ...

Page 7: ...no maintenance It is hermetically sealed properly lubricated at the factory and should provide years of satisfactory operating service Should the refrigerant charge be lost recharging ports access fittings on the suction and discharge sides of the compressor are provided for recharging and or checking suction and discharge pressures Under no circumstances should the access fitting covers be loosen...

Page 8: ...t grille To remove the grille remove 2 screws and pull top edge of grille forward The filter may now be removed and cleaned or new filter installed Reinstall grille Cleaning Instructions 1 Flush the filter with warm water from the exhaust side to the intake side DO NOT USE CAUSTICS 2 After flushing allow filter to drain Placing it with a corner down will assure complete drainage 3 Recoat the filte...

Page 9: ...Is there airflow YES proceed to step 6 NO possible Defective thermostat Open motor winding Stuck blower motor Obstructed wheels blades 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm YES wait 5 minutes then proceed to step 7 NO possible Defective thermostat Defective capacitor Defective overload Defective relay ...

Page 10: ...ut won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad relay Bad overload switch Bad run start capacitor Unit blows breakers Under sized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in For additional technical information i e amp draw pressures temperatures co...

Reviews: