DESIGN DATA

Model

Voltage

Hz

Full Load 

Amps

Phase

BTU/Hr

Max F (C) 

Water 

Temp.

Max Water 

Usage 

(GPM)**

Shipping 

Weight

lbs (kg)

LB110216GWXXX

115

50/60

7.6/6.8

1

2000/2000

90 (32)

0.5

84 (38)

LB110226GWXXX

230

50/60

3.8/3.4

1

2000/2000

90 (32)

0.5

84 (38)

LB110416GWXXX

115

50/60

7.7/7.2

1

3900/4000

90 (32)

0.5

84 (38)

LB11426GWXXX

230

50/60

3.9/3.6

1

3900/4000

90 (32)

0.5

84 (38)

** Rated 90 F (32 C) inlet water and full air conditioning load. Actual usage will vary.

BENCH TESTING

To avoid possible damage to the air conditioner, it must be in 

an upright (vertical) position for a minimum of five (5) minutes 

before functional testing is started.

CAUTION

When “Bench Testing” the air conditioner before mounting to the electronic enclosure, follow the procedures 

outlined in the following paragraphs:

•  Refer to name plate for proper electrical current requirements, then connect the power cord to a properly grounded 

electrical outlet.

•  Connect to clean, pressurized, water supply and provide drain.

NOTE:

Minimum circuit ampacity should be at least 125% of the amperage shown in the DESIGN 

DATA section. To prevent overloading, no other equipment should be connected to this 

current.

•  Make sure the unit has been in the upright (operating) position for at least 5 minutes.

•  Operate the air conditioner for five (5) or (10) minutes. No excessive noise or vibration should be evident during this 

run period. The evaporator or cool air blower located on the upper portion of the unit and the compressor should 

be running. To check cool air output, use a reliable air temperature measuring device. The cool air output should be 

between 50 F to 60 F (10 C to 16 C) when room temperature is between 70 F to 80 F (21 C to 27 C).

•  You may remove the front panel to further check the operation. The discharge line from he compressor (the 

uninsulated line) should become very warm. Condenser water should begin to flow from the outlet port soon after 

start-up and continue for a short time after shut-down.

•  The compressor is provided with automatic reset thermal overload protection. This thermo switch is located and 

mounted inside the plastic enclosure clipped to the compressor. The only time this switch should operate is when 

the compressor overloads due to amperage exceeding nameplate rating. The thermal overload switch will actuate 

the stop compressor operation. The blower will continue to operate and water will continue to flow for a short time. 

The compressor will not restart until the compressor has cooled and the thermal overload has reset.

•  The unit will also shut down if water supply is interrupted. See WATER USAGE, page 8.

RSPSupply  -  1-888-532-2706 -  www.RSPSupply.com

http://www.RSPSupply.com/p-19626-Hoffman-LB110426GW010-Water-Cooled-Rack-AC-230V-4000-BTU-Indoor.aspx

Summary of Contents for LB110216GW Series

Page 1: ...8707 Rev E P N 10 1008 51 Water Cooled Rack Mount Air Conditioner LB11WC Model INSTRUCTION MANUAL RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 19626 Hoffman LB110426GW010 Water Cooled Rack AC 230V 4000 BTU Indoor aspx ...

Page 2: ...tion compressor is filled with lubricating oil Running the compressor without oil in the lower part of the compressor housing will cause permanent damage to the unit This also voids the warranty CAUTION TABLE OF CONTENTS HANDLING 2 DESIGN DATA 3 BENCH TESTING 3 INSTALLATION 4 PRINCIPLES OF OPERATION 6 MAINTENANCE 7 Compressor 7 Evaporator Blower 7 Refrigerant Loss 7 WATER USAGE 8 Condenser 8 Reset...

Page 3: ...erate the air conditioner for five 5 or 10 minutes No excessive noise or vibration should be evident during this run period The evaporator or cool air blower located on the upper portion of the unit and the compressor should be running To check cool air output use a reliable air temperature measuring device The cool air output should be between 50 F to 60 F 10 C to 16 C when room temperature is be...

Page 4: ...e as preferred The 3 8 inch I D flexible P V C drain tube which exits at the rear of the air conditioner must be routed to the exterior of the electronic enclosure A P trap is built into the air conditioner to prevent ambient air from entering the enclosure via the drain system No addition P trap is required Make sure that the drain tube plastic plug is removed and discarded or flooding problems w...

Page 5: ...Dashed lines represent air conditioner Figure 3 CUT OUT DIMENSIONS FOR NEMA 12 ENCLOSURES DRAIN PLUG Figure 4 RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 19626 Hoffman LB110426GW010 Water Cooled Rack AC 230V 4000 BTU Indoor aspx ...

Page 6: ...he air conditioner is momentarily interrupted and immediately reapplied within 3 to 5 seconds the compressor may not restart due to the high back pressure of the compressor NOTE Do not attempt to restart the air conditioner for at least one 1 minute after the unit has been accidentally or intentionally shut off It takes a minimum of one 1 minute after shut down for the compressor suction and disch...

Page 7: ...ubricated during manufacturing for the life of the motor Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly deteriorate filter condenser coils blowers motors etc CAUTION REFRIGERANT LOSS Your Hoffman cooling air conditioner was thoroughly tested before leaving the factory to insure against refrigeration leaks Shipping damage or microscopic leaks not fou...

Page 8: ...in Figure 5 Should the water supply be cut off for any reason the reset button will trip shutting off the air conditioner After restoration of the water supply the unit can be restarted by pushing the reset Pushing this button should restore proper function of the air conditioner Overloading of the air conditioner may also cause the reset button to trip The valve that controls the flow of condensa...

Page 9: ...dually diminish to zero If water flow persists it may indicate a malfunction of the control valve Information on the specific valve employed is supplied with the air conditioner FREEZING AND DRAINING THE SYSTEM The air conditioner can be severely damaged by freezing if not properly drained Damage due to freezing is not covered by the warranty WARNING If the unit is to be shipped to or stored in an...

Page 10: ...3 Pentair Equipment Protection 89048707 10 DIMENSIONAL DRAWING RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 19626 Hoffman LB110426GW010 Water Cooled Rack AC 230V 4000 BTU Indoor aspx ...

Page 11: ...Filter Drier 52 6028 00 Same Not Pictured Mounting Gasket Kit 11 1029 00 Same 3 Evaporator Blower 30 4019 01M 30 4019 02M 4 Compressor 10 1016 22 10 1026 74 Not Pictured Thermal Overload 10 1007 44 10 1007 57 Not Pictured Compressor Relay 10 1028 05 10 1028 07 Not Pictured Start Capacitor None 10 1032 09 RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 19626 Hoffman LB110426GW01...

Page 12: ... Pentair Equipment Protection 89048707 12 WIRING SCHEMATICS 115V RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 19626 Hoffman LB110426GW010 Water Cooled Rack AC 230V 4000 BTU Indoor aspx ...

Page 13: ... 2013 Pentair Equipment Protection 89048707 13 220 V RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 19626 Hoffman LB110426GW010 Water Cooled Rack AC 230V 4000 BTU Indoor aspx ...

Page 14: ...urrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself Failure to provide such prompt notice to Pentair Equipment Protection shall result in forfeiture of Buyer s rights under this warranty In the event of a warranty claim Buyer is to return defective goods to Pentair Equipment Protection in accordance with P...

Page 15: ...le goods at no charge Failure analysis for non warranty repairs are subject to a 100 per hour Engineering charge plus any other incurred testing costs F All returned merchandise must be sent to the following address Pentair Equipment Protection Cooling Technology 2100 Hoffman Way Anoka MN 55303 1745 G Credit for accepted returns shall be at the original selling price or the current selling price w...

Page 16: ...air Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairEquipmentProtection com RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 19626 Hoffman LB110426GW010 Water Cooled Rack AC 230V 4000 BTU Indoor aspx ...

Reviews: