MASTER PROGRAMMING MODE

When the Master Programming Mode is entered, all available 

option setting displays may be viewed and set as needed. 

Depending on current option settings, some parameters 

cannot be viewed or set.

Setting the Time of Day

1.  Press and hold either the Up or Down buttons until the 

programming icon replaces the service icon and the 

parameter display reads TD.

2.  Adjust the displayed time with the Up and Down buttons.
3.  When the desired time is set, press the Extra Cycle button 

to resume normal operation. The unit will also return to 

normal operation after 5 seconds if no buttons are pressed.

Entering Master Programming Mode

Set the Time Of Day display to 12:01 P.M. Press the Extra Cycle 

button (to exit Setting Time of Day mode). Then press and hold 

the Up and Down buttons together until the programming 

icon replaces the service icon and the Display Format screen 

appears. 

Exiting Master Programming Mode

Press the Extra Cycle button to accept the displayed settings 

and cycle to the next parameter. Press the Extra Cycle button 

at the last parameter to save all settings and return to normal 

operation. The control will automatically disregard any 

programming changes and return to normal operation if it is 

left in Master Programming mode for 5 minutes without any 

keypad input.

Resets

Soft Reset: 

Press and hold the Extra Cycle and Down buttons 

for 25 seconds while in normal Service mode.  This resets all 

parameters to the system default values, except the volume 

remaining in meter immediate or meter delayed systems and 

days since regeneration in the time clock system.

Master Reset: 

Hold the Extra Cycle button while powering up 

the unit. This resets all of the parameters in the unit. Check 

and verify the choices selected in Master Programming Mode.

1. Display Format (Display Code DF)

This is the first screen that appears when entering Master 

Programming Mode. The Display Format setting specifies 

the unit of measure that will be used for volume and how 

the control will display the Time of Day. This option setting is 

identified by “DF” in the upper left hand corner of the screen. 

There are three possible settings:

Display Format Setting

Unit of Volume

Time Display

GAL

U.S. Gallons

12-Hour AM/PM

Ltr

Liters

24-Hour

2. Valve Type (Display Code VT)

Press the Extra Cycle button. Use this display to set the Valve 

Type. The Valve Type setting specifies the type of cycle that the 

valve follows during regeneration. Note that some valve types 

require that the valve be built with specific subcomponents. 

Ensure the valve is configured properly before changing the 

Valve Type setting. This option setting is identified by “VT” in 

the upper left hand corner of the screen. There are 5 possible 

settings:

Abbreviation

Parameter

dF2b

Standard Downflow, Double Backwash  

(7000 Default)

Fltr

Filter (7000 Default)

dFFF

Down Flow Fill First

AIO

Air Injected Oxidizer (AIO)

3. Control Type (Display Code CT)

Press the Extra Cycle button. Use this display to set the 

Control Type. This specifies how the control determines when 

to trigger a regeneration. For details on how the various 

options function, refer to the “Timer Operation” section of this 

service manual. This option setting is identified by “CT” in the 

upper left hand corner of the screen. There are four possible 

settings:
Meter Delayed:          Fd
Meter Immediate:     FI
Time Clock:                tc
Day of Week:              dAY
Variable Reserve:      fdPb

4. Number of Tanks (Display Code NT)

Press the Extra Cycle button. Use this display to set the 

Number of Tanks in your system. This option setting is 

identified by “NT” in the upper left hand corner of the screen. 

There is one possible settings
Single Tank System:    1

Summary of Contents for Fleck7000SXT

Page 1: ...FLECK 7000SXT SERVICE MANUAL...

Page 2: ...water systems only This product must be installed in compliance with all state and municipal plumbing and electrical codes Permits may be required at the time of installation It is established that wh...

Page 3: ...gallon setting J 3 Ext Range 18 750 318 750 gallon setting K Electronic________Pulse Count________Meter Size 4 System Type A System 4 1 Tank 1 Meter Immediate or Delayed Regeneration B System 4 Time...

Page 4: ...hould be the same size as the drain line flow control 4 Refer to the dimensional drawing for cutting height of the distributor tube If there is no dimensional drawing cut the distributor tube flush wi...

Page 5: ...that continues to keep time and the passage of days for a minimum of 48 hours in the event of power failure During a power outage the control goes into a power saving mode It does not monitor water us...

Page 6: ...mal step timing Control Operation During Programming The control only enters the Program Mode with the valve in service While in the Program Mode the control continues to operate normally monitoring w...

Page 7: ...election SF rc cr SF Safety Factor Percentage off of gallon remaining capacity RC Fixed Reserve Capacity Fixed Gallon Amount CR Variable Reserve Changes the reserve based on previous day s water usage...

Page 8: ...s in the unit Check and verify the choices selected in Master Programming Mode 1 Display Format Display Code DF This is the first screen that appears when entering Master Programming Mode The Display...

Page 9: ...cifies what percentage of the system capacity will be held as a reserve Since this value is expressed as a percentage any change to the unit capacity or feedwater hardness that changes the calculated...

Page 10: ...D5 D6 and D7 in the upper left hand corner of the display Set the value to ON to schedule a regeneration or OFF to skip regeneration for each day Use the Up and Down buttons to adjust the setting as n...

Page 11: ...service and the time of day is NOT set to 12 01 PM 2 Use this display to adjust the Day Override This option setting is identified by DO in the upper left hand corner of the screen 3 Press the Extra C...

Page 12: ...le buttons for five seconds while in service 2 Use this display to view the current Flow Rate This option setting is identified by FR in the upper left hand corner of the screen 3 Press the Up button...

Page 13: ...Back Plate 10 3 40967 Screw Slotted Hx Wshr Hd 1 4 20 x 1 LG 11 5 13602 Screw Phil Rd Hd 6 32 x 5 16 12 1 12473 Screw Hx Wshr Hd 10 24 x 625 13 2 11805 Screw Rd Hd 4 40 x 5 8 Type POWERHEAD ASSEMBLY B...

Page 14: ...4 3 0 gpm 61455 35 DLFC 3 4 3 5 gpm 61455 40 DLFC 3 4 4 0 gpm 61455 45 DLFC 3 4 4 5 gpm 61455 50 DLFC 3 4 5 0 gpm 61455 60 DLFC 3 4 6 0 gpm 61455 70 DLFC 3 4 7 0 gpm 61456 00 DLFC 1 Blank 61456 8 0 D...

Page 15: ...Rev A 2 61562 Connector Assembly 1 1 2 NPT 7000 Brass 2 61562 10 Connector Assembly 1 1 2 BSP 7000 Brass 2 42241 01 Connector Assembly 1 1 2 NPT 7000 Plastic 2 42241 11 Connector Assembly 1 1 2 BSP 70...

Page 16: ...kt Hd Set 10 24 x 75 4 1 19805 Nut Hex 10 24 Nylon Black 5 1 19652 01 Poppet Assy SBV w O ring 6 1 19649 Flow Dispenser 7 1 11183 O Ring 017 8 1 19647 Elbow Safety Brine Valve 9 2 19625 Nut Assy 3 8 P...

Page 17: ...al through drain line Air in water system Assure that well system has proper air eliminator control Check for dry well condition Improperly sized drain line flow control Check for proper drain rate Ir...

Page 18: ...it is measuring flow by running service water and watching for the flow indicator on the display If the unit does not measure flow verify that the meter cable is connected properly and that the meter...

Page 19: ...the left side of the board with the flexible finger on the powerhead Apply pressure to the left while rotating the board back 41033 REV B Figure 4 2 When all the way down snap the circuit board into...

Page 20: ...REV A 41121 REV A Backwash Position 40988 REV A 41121 REV A Brine Position 40988 REV A 41121 REV A Slow Rinse Position 40988 REV A 41121 REV A Second Backwash Position 40988 REV A 41121 REV A Rapid R...

Page 21: ...FLECK 7000SXT Service Manual 21 INJECTOR FLOW DATA TR18755 REV B...

Page 22: ...22 FLECK 7000SXT Service Manual METER FLOW DATA TR18753 Softener TR18688 Filter 41140 02 REV A 41023 REV C DIMENSIONS...

Page 23: ...FLECK 7000SXT Service Manual 23...

Page 24: ...trademarks and logos are the property of their respective owners Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notic...

Reviews: