INTERFACING WITH THE XTR2 CONTROL
NOTE: See the
Fleck 5800 or 5810/5812 XTR2 Service Manuals
for complete XTR2 programming information.
Connecting to the XTR2 Control
1. From the XTR2 Control Home screen, press the Settings
button to display the Settings screen, then press the
Settings button again. A warning message appears.
2. Press
to continue to the Password screen. The
Password screen displays a numeric keypad. Enter the
master settings password
1201
and press
to continue to
the main Master Settings screen.
3. From the main Master Settings screen press the
format
button to display the Format screen.
Figure 7 Format Screen
4. Press on the Format screen to display the USB screen.
Figure 8 USB Screen
5. When the USB screen appears, connect a USB cable to the
USB port on the control circuit board.
Figure 9 XTR2 Control Circuit Board
USB Connection for
Field Programming
TANK SENSOR
REMOTE LOCK
START
MOTOR
HOME 1
FLOW
12V DC
AUX 2
AUX 1
USB
RESET
SWITCH
TOUCH SCREEN
PRODUCTION
TEST PORT
CHLORINE
GENERATOR
FUTURE USE
HOME 2
COMM PORT
COMM
NO
NC
COMM
NO
NC
+
_
+
--
SIGNAL
POS
GND
PHOTO
INTERRUPTER
MOTOR
LOCK
START
GND
OPTIONAL
REMOTE
SIGNAL START
SWITCH (N.O.)
OPTIONAL
INTERLOCK
SWITCH (N.O.)
CLOSED
CONTACT
PREVENTS
REGENERATION
IF ENABLED
CLOSED
CONTACT
INITIATES
REGENERATION
IF ENABLED
5A / 250V Max
6. Connect the other end of the USB cable to the PC with the
Field Programmer software installed.
NOTE: Do not remove USB cable from computer or control
while connected and transferring data.
7. Upon initial connection of the control to the PC, your
PC may configure the drivers necessary for connection
to the control. Please wait until driver configuration is
complete before continuing. A
connection established
message appears on the control screen when a successful
connection to the PC has been made.
NOTE:
Pressing the Settings button on the XTR2 control
will disconnect the control from the PC and return the
display to the Master Settings screen. Do not press
until you are ready to disconnect.
8. If you have not already done so, launch the Field
Programmer software on your PC by double-clicking on
the Pentair Field Programmer icon or selecting the menu
item from the Start menu. The Field Programmer Master
Programming Settings window appears (see Figure 2).
9. When a successful connection between the PC and control
has been made, the USB icon in the upper-right corner of
the Field Programmer window turns green and displays
the message
XTR2 detected
. You can now begin
transferring data.
Figure 10 XTR2 Control Successfully Connected
Uploading Programmed Settings to the XTR2
Control
1. After all programming within the Field Programmer is
complete, click the icon in the Field Programmer
application to upload all settings configured in the Field
Programmer to the XTR2 control. A small window will
appear showing progress of the data transfer. The
application will display a message when transfer is
complete. Click the message to clear it from the screen.
Figure 11 Communication Complete Message
2. Click the icon in the Field Programmer application to
set the time and day of week in the XTR2 control to match
the time currently set on your PC. Click the
communication
complete
message that appears to clear it from the
screen.
Downloading Diagnostic Data to the Field
Programmer Application
1. After establishing a connection between the Field
Programmer application and the XTR2 control, click the
icon in the Field Programmer application to download
diagnostic data from the control. Click the
communication
complete
message that appears to clear it from the
screen.