POSITIONING THE SENSOR

Position the RTD sensor in the lower quadrant of the pipe as shown 
in the diagram.

 Place the RTD sensor at least 3 feet (1 m) from 

pipe supports, valves, or other heat sinks. 

Tape the sensor firmly 

WRWKHSLSHZLWK$7DOXPLQXPWDSHPDNLQJVXUHWKHUHLVQRDLU

space between the sensor and the pipe. 

Do not use the same piece 

of AT-180 tape to overlap the RTD and heat-trace cable.

90

Heating cable

Control sensor

AT-180 tape

AT-180 tape

Heating cable

Control 
thermostat bulb

Double traced

Single traced

ROUTING THE RTD

Electrical Wiring Guidelines:

0RVWHOHFWULFDOFRGHVVXFKDV1(&SHUPLW&ODVVFLUFXLWV

to occupy the same cable, enclosure, or raceway without regard 

WRZKHWKHUWKHLQGLYLGXDOFLUFXLWVDUHDOWHUQDWLQJFXUUHQWRUGLUHFW
FXUUHQWSURYLGLQJDOOFRQGXFWRUVDUHLQVXODWHGIRUWKHPD[LPXP
YROWDJHRIDQ\FRQGXFWRUVLQWKHFDEOHHQFORVXUHRUUDFHZD\

RTD Direct Connection to Controller

 

The RTD50CS can be terminated directly at the controller using 
the  supplied 1/2-inch NPT fitting. In this configuration, no addi-
tional  extension wire is required. 

RTD50CS WIRING

Connect the wires as shown.

 

Note:

 Ground RTD extension wire shield at one end only,  

preferably at DigiTrace electronics end.

Red (Source)

White

Red

Red

Red (Compensate)

Field Wiring (if required)

White (Common return)

Ambient sensing

RTD50CS

RTD50CS

DigiTrace C910
or ACCS-30
electronic
controller

XL-Trace

Typical Fire Sprinkler Freeze Protection System

End Seal

DigiTrace C910 
or ACCS-30
electronic
controller

RTD50CS

Typical Freezer Frost Heave Prevention System