Figure 1. Heat-tracing control
Cir
cuit
1Cir
cuit
2
G
Ø
Ø
Heating
cable
Power
connection
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Braid
Control
thermostat
Relay
GFEPD
Power supply
208-V or 240-V supply – 240-V heater
G
Ø
Ø
WIRING
INSTALLING THE THERMOSTAT
1. Verify that the thermostat
is suitable for the area
where it is to be installed.
2. Check the line voltage and
the heat-tracing load to
ensure that the thermostat
ratings are not exceeded.
3. Mount the unit using unistrut or the universal mounting
bracket (UMB-263757) in a position that prevents condensation
from draining into the enclosure from the connecting conduit
(see diagram above).
pOSITIONING THE SENSOR BULB
4. Position the bulb in the
lower quadrant of the pipe
as shown in the diagram
to the left. Place the bulb
at least three feet from
pipe supports, valves, or
other heat sinks; protect
the capillary from kinks or
bends less than 1⁄2 inch in
radius.
5. Tape the bulb firmly to the pipe with AT-180 aluminum tape,
making sure there is no air space between the bulb and pipe.
Do not overlap the bulb and heating cable with the same piece
of AT-180 tape.
6. For metal-tank-wall sensing, use the BCK-35 bulb clamp
(purchased separately from Pentair Thermal Management)
and install the clamp per the instructions provided. Make sure
there is no air space between the tank wall and the bulb.
For installation on plastic tanks, contact Pentair Thermal
Management at (800) 545-6258.
SETTING THE THERMOSTAT
7. Set the thermostat dial to the desired temperature, then finish
wiring.
8. Complete insulating. Do not turn the system on until the bulb is
covered with thermal insulation.
9. Fill the piping or tank. Once the thermostat has begun to cycle,
check the fluid temperature with an immersed thermostat
(best for plastic systems) or an accurate temperature indicator.
Adjust the dial setting, if necessary.
Conduit
drain
90
Heating cable
Control thermostat bulb
AT-180 tape
AT-180 tape
Heating cable
Control thermostat bulb
Double traced
Single traced