background image

2

AViD

 LP R2

InstallatIon and operatIng InstructIons

3.0 FielD wiring

Attention

Before installing the conduit entry gland, please 
ensure that it is the correct size and thread form. 
An incorrect gland may affect the enclosure 
ingress protection rating.

3.1  The terminal strip base has been 

designed to offer easy access for wire 
termination.

3.1a  It is not necessary to remove the terminal 

strip to connect the field wiring, but if 
required, first remove the terminal strip 
retaining screw and keep safe as this will 
be required to secure the terminal strip 
when complete.

3.1b  Lift the terminal strip evenly off of the 

two base pins and terminate the wiring 
in accordance with the wiring diagram 
which is located on the of the cover.

note

For special builds of the AVID LP product it may be 
necessary to have an additional A4 wiring diagram 
placed in the packing box.

3.1c  Position the terminal strip over the 

two base pins and press evenly in the 
direction of the pins.

3.1d  Secure with the retaining screw removed 

in step 3.1a.

4.0 eAsiFix cAM setting

4.1  To set the switch or sensor cam (Fig. 3), 

lift the bottom cam and turn until 
switch / sensor is activated and then 
release. The spring will push the cam 
back onto the splined shaft.

4.2  Operate the actuator to the opposite 

extreme, push down on the top cam 
and turn until the upper switch / sensor 
is activated.

4.3  Operate the actuator from one extreme 

to the other several times to ensure that 
the switches / sensors activate correctly.

5.0 coVer AsseMbly

5.1  Before assembling the cover assembly to 

the AVID LP housing, check the cover seal 
detail to ensure that it is not damaged 
and free of debris.

5.1  Engage the shaft into the beacon bore 

and rotate the cover assembly so that the 
shaft drive flats fully engage.

5.2  Approximately align the cover with the 

housing flange and secure using either 
a 8 mm A/F spanner / socket drive or an 
appropriately sized flat blade screwdriver.

5.3  Tighten the screws to a torque value of 

18 to 22 Lb/Ins.

6.0 reADy For use

6.1  The AVID LP switchbox is now ready 

for use.

6.2  If there are any un-used conduit entries, 

please ensure that they are plugged using 
correctly rated IP blanking plugs.

7.0 technicAl DAtA

Area classification - non hazardous.
Ingress protection - IP66 / 67

switch / sensor options

Mechanical Switch – SPDT Form C, 
Electrical rating -
  24, 48, 110 & 240 VAC / 15Amps,
  24 VDC / 15 Amps
  48 VDC / 2.5 Amps

Alternative inductive proximity sensors;

  P&F - NJ2-V3-N, NBB3-V3-Z4, NBB2-V3-E2
  IFM - IS5026, IS5001, IS0003, IS5003, NS5002
  Turck - Bi2-Q10S-AP6X, Bi2-Q10S-YOX
  Telemecanique - XS7-H10PA340

Terminal strip –
Weco 302 HDS, 8 points or Klippon MK3, 
6 points.
Conduit options –
Up to 2 x M20 x 1.5p or ½”-14 NPT
Ambient Temperature Range –
Minus 20°C to +80°C

Figure 3

Top Cam (OPEN) 

Push down, turn 

and release.

Bottom Cam 

(CLOSED). Lift, turn 

and release.

Reviews: