background image

Rev. B  4-5-02

             P/N 472089

9

Installation (Operating Controls)

Knob Stopper

Screw A

OPERATING (CONTROLS)

Dual Temperature Control System

For convenience and economy all MiniMax NT
Heaters are equipped with two thermostats on the
front of the heater control panel; see Figure 8.

Figure 8.

Figure 9.

THERMOSTAT KNOB STOPPER

Each thermostat is equipped with a mechanical stop that
can be locked or unlocked with use of a screwdriver to
prevent temperatures in excess of that desired by the user;
see Figure 9.
The maximum setting can be adjusted by loosening the screw
"A" and turning the stopper dial to desired maximum setting.
Lock the setting by tightening the screw. The Mechanical
stop is under the knob. Ensure that the knob is stopping at the
correct position when the knob is rotated clockwise from a
lower temperature position. (See Thermostat Adjustment.)

NOTE

To eliminate error due to piping heat losses,
measure pool temperature with an accurate
thermometer directly at the pool or spa.

THERMOSTAT ADJUSTMENT

The knob with locking feature eliminates the need for
constant thermostat adjustments. Set the knob pointer to
the desired pool or spa temperature.
If further adjustment is needed, rotate the knob until the
desired temperature is obtained. This knob position
corresponding to your desired maximum pool or spa
temperature may now be preset (locked) by the knob
stopper which prevents the knob from being turned beyond
the maximum temperature you set.

POWER (THERMOSTAT SELECT) SWITCH

The Pool/Off/Spa switch allows the heater to be turned off
when heating is not desired.

1. “Pool” position - Maintains selected pool

temperature.

2. “Off” position - Heater will not come on regardless

of drop in pool or spa temperature.

3. “Spa” position - This allows separate control of spa

water temperature.

INDICATOR LIGHT DESCRIPTION

The MiniMax NT Heater provides nine status indicator lights, six can be seen from the front of the control panel which
help you understand the operation of the heater. If something should go wrong, the lights will aid in troubleshooting the
problem. Three additional lights can be seen after opening the control panel. These three lights give the service technician
advanced troubleshooting capability. All the LED lights are green with the exception of the red service LED.

POWER LIGHT (POWER)

The light is on at all times, in any switch position, indicating
24 VAC power is being supplied to the control circuit. If it
fails to light, no other light will be on. Possible causes are:
a) external power to the heater is disconnected, check
service panel circuit breaker or fuses; b) local circuit
breaker inside the transformer has tripped -- investigate
cause before resetting; c) transformer has failed.

THERMOSTAT (TSTAT)

This light is on when the thermostat contacts close, signaled
by the water temperature falling below the setpoint, calling
for the heater to fire to maintain the desired water
temperature.

AUXILIARY (AUX)

This light is on when it indicates the remote switch contacts
are closed. This allows you to observe if your remote switch
is properly closing the heater control circuit. When shipped
from the factory a jumper is installed to maintain closed
circuit in the absence of a remote switch.

PRESSURE (PRESS)

This light is on when Spa/Pool Selector switch is on,
indicates the circulation pump is running properly. If
pressure light fails to light, the pump may have lost its
prime or water flow may be restricted by an inadvertently
closed valve or clogged filter or pump basket. If you have
determined that there is no water flow restriction to the
heater, you should call a qualified serviceman.

Summary of Contents for MiniMax NT Low NOx 200

Page 1: ...ation and service must be performed by a licensed qualified installer service agency or the gas supplier MiniMax NT Low NOx Series POOL SPA HEATERS OPERATION INSTALLATION MANUAL WARNING WHAT TO DO IF...

Page 2: ...stallation Water Connections 13 Installation Plumbing 13 Installation Gas Line 14 Pipe Sizing Chart Gas Pressure Requirements 14 Regulated Manifold Pressure Test 14 Venting Indoor Installations 15 18...

Page 3: ...the MiniMax NT Low NOx pool and spa heater The manufacturer s warranty may be void if for any reason the heater is improperly installed and or operated Be sure to follow the instructions set forth in...

Page 4: ...e with an accurate thermometer Spa or hot tub thermostats may err in regulating water temperatures by as much as 4 F 5 Persons with a medical history of heart disease circulatory problems diabetes or...

Page 5: ...G OPERATION NATURAL GAS 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off electric power to the heater 4 This heater is equipped with an ignition device wh...

Page 6: ...state be sure your contractor bears the appropriate license SPECIFICATIONS 24 05 2 in SOCKET A DIM 8 84 6 64 30 63 LEG LEG 14 50 3 50 4 875 MODEL 200 250 24 63 21 63 A DIM 15 50 300 400 34 13 27 63 7...

Page 7: ...supplied with this heater must be replaced installer must supply No 18 AWG 600V 105 C U L approved AWM low energy stranded copper wire or it s equivalent Thermal fuse wiring must be replaced with 18...

Page 8: ...NITION MOD EXT SWITCH THERMOSTAT CIRCUIT BOARD JUMPER REQUIRED IF NO 2 WIRE REMOTE SWITCH POOL OFF SPA FRONT PANEL THERMOSTAT SELECT SWITCH TFUSE VALVE REMOTE POOL OFF SPA THERMOSTAT SELECT SWITCH PRE...

Page 9: ...ture 3 Spa position This allows separate control of spa water temperature INDICATOR LIGHT DESCRIPTION The MiniMax NT Heater provides nine status indicator lights six can be seen from the front of the...

Page 10: ...CUIT BLOCK CURRENT SWITCH OR DEVICE CLOSED CIRCUIT PASS CURRENT THERM AUX PRESS HEAT POWER SERVICE FRONT PANEL LEDS FRONT PANEL LEDS HEAT PRESS AUX THERM SERVICE POWER OR POOL OFF SPA THERMOSTAT SELEC...

Page 11: ...ERM INCOMING LINE VOLTAGE THERMOSTAT PWR BREAKER CIRCUIT TSTAT RELAY RMT REMOTE THERMOSTAT CIRCUIT BOARD NO MV CLOSE IF IGNITION MODULE SRVE HI TEMP LIMIT SWITCHES HI TEMP TFUSE MV IND TFUSE GND THERM...

Page 12: ...WHT LOW GAS F1 F2 24 VAC WHT POOL JUMPER REQUIRED J6 PROBE TEMP VLV TPROBE J5 J8 24V J4 J7 IGN MODULE J10 J11 IND PRESSURE SW IF ORIGINAL FACTORY WIRING MUST BE REPLACED INSTALLER MUST SUPPLY UL CSA...

Page 13: ...perature sensing bulb from the inlet outlet header Note If needed you may cut the wire ties holding them together 5 Remove the 16 bolts holding the main inlet outlet head and return head in place exch...

Page 14: ...n must be leak tested before placing the heater in operation Do not use flame to test the gas line Use soapy water or another nonflammable method A manual main shut off valve must be installed externa...

Page 15: ...ombustible materials must be maintained in accordance with type of vent pipe employed in the absence of a clearance recommendation by the vent pipe manufacturer the requirements of the Uniform Mechani...

Page 16: ...on combustible floor or on a non combustible base and in an area where leakage from heat exchanger or water connections will not result in damage to the area adjacent to the heater or the structure Wh...

Page 17: ...be contaminated by corrosive chemical fumes which can void the warranty NOTE The openings listed in Table 2 are free open vent area if the vents incorporate restrictive louvers the vent openings must...

Page 18: ...walkways must be at least 3 ft above any outside air intake located within a 10 ft radius must NOT be within 3 ft of an inside corner of the structure must be at least 1 ft above grade must be located...

Page 19: ...drainage Maintain minimum clearances as indicated below Install a minimum of 4 feet below and 4 feet horizontally from any opening to a building see Figure 18 IMPORTANT When locating the heater consid...

Page 20: ...is running and is primed to close water pressure switch and supply power to heater 2 Set thermostat to lowest setting 3 Set the thermostat rocker switch to the center OFF position 4 Open the access do...

Page 21: ...re than a 3 ft elevation difference between the heater heat exchanger and the pool water line if this is the case the water pressure switch must be reset to maintain open switch contacts with no water...

Page 22: ...r is activated for a heat up period followed by energization of the gas valve for the trial for ignition period When flame is detected during the trial for ignition the ignitor is deactivated and the...

Page 23: ...thermostat knob stopper 5 Set time clock to start circulation system no earlier than daybreak The swimming pool loses less heat at this time 6 For pools that are only used on the weekends it is not ne...

Page 24: ...Then test only once every month or so to be sure it is being maintained See your local pool dealer for help in properly balancing the water chemistry 7 2 6 8 7 0 7 4 7 6 7 8 8 0 8 2 8 4 Add Soda Ash...

Page 25: ...ter operating after pump has shut off Shut off gas supply and call serviceperson Heater exchanger scaled Shut off gas supply and call serviceperson Troubleshooting General SERVICE CHECKS IGNITION MODU...

Page 26: ...X NT LOW NOx HEATER Dual Voltage 1 4 3 5 7 8 9 11 28 30 35 36 38 51 50 48 46 44 45 40 39 17 16 15 14 23 13 34 41 26 27 2 6 10 24 25 22 18 31 33 32 37 47 43 42 12 29 19 20 21 MiniMAX NT Low NOx Heater...

Page 27: ...old Assy 1 472004 472003 472002 472001 32 Burner 4 5 6 8 200 250 300 400 33 Face Plate 1 472069 472068 472067 472052 34 Jacket Upper Panel Left 1 35 Jacket Corner 4 36 Jacket Divider 1 471827 471651 4...

Page 28: ...dent negligence alteration abuse misapplication or misuse The above warranty applies only if the heater is installed and operated in complete compliance with the installation and operation manual prov...

Reviews: