For installations in areas subject to explosion hazards, special 
regulations apply! 

APPLICATION

Submersible pumps of the oxylift 2 range are suitable for dos-
ing and pumping wastewater in small-scale clarification plants.

WARNING!

The pump must only be connected to sockets that have been 
installed properly in accordance with the regulations and are 
protected with at least 10 A (slow) and RCD-safety switches 
(30mA).

DANGER!

The pump must never be used when a person is in the water.

Modes of operation

Pumped medium at a temperature of 95°F (35°C): continuous 
operation S1.
Pumped medium at a temperature of 140°F (60°C): 
intermittent operation S3, 40%,  
i.e. 4 min. operation and 6 min. interval.
The submersible pump is frost-resistant down to -4°F (-20°C) 
when stored in dry conditions. When installed, however, it 
must not be allowed to freeze in the water.

Transport

The pump must always be lifted by the handle and never by the 
power supply cable or the float of the level control! The pump 
should only be lowered into deeper chambers or pits using a 
rope or chain.

ELECTRICAL CONNECTION

NOTICE!

  Only  qualified  electricians  may  carry  out  electrical 

works to the pump or the controls. 

The relevant standards (such as EN standards), country-spe-
cific regulations (such as VDE in Germany), and the regulations 
of the local power supply companies must be observed.

NOTICE!

 

Never put the free lead end in water! If water gets into 

the plug, this can cause malfunctions and damage.

Observe the operating voltage (see the type plate)!
No additional motor protection is required, since the system 
has an integrated winding thermostat. Inadmissible tempera-
tures and operating times will result in the thermostat switch-
ing the system off (please refer to the section entitled Appli-
cation). After the thermostat has switched off the system, pull 
out the mains plug before remedying the fault, since the device 
can switch itself on again automatically after cooling down if 
the power is still connected! 

Replacing the connection cable

Only use original manufacturer’s parts. We recommend replac-
ing the seal and the screws each time the connection cable is 
replaced.

NOTICE!

 

When the connection cable is loosened, the motor 

compartment is opened. Please ensure clean and dry condi-
tions when handling the device.

NOTICE!

 

Do NOT use a power screwdriver. A size 2 PZ screwdri-

ver must be used to unscrew and tighten the connection cable.

Grease the sealing ring with Vaseline before inserting the car-
tridge. Then tighten the screws by hand (max 1 Nm). 

INSTALLATION

The pump must be securely fixed to ensure that it does not be-
come detached during operation. The pump should be fixed at 
the control head and the discharge branch.

Venting the pump housing

The pump can be vented by providing a 6 mm drill-hole in the 
pump housing. This drill-hole allows the pump housing to be 
reliably vented even if a non-return valve is used.

NOTICE!

 

If the pump is malfunctioning, a slight leakage of the 

contents of the oil reservoir into the pumping medium is pos-
sible.

3

Summary of Contents for OXYLIFT 2

Page 1: ...JUNG PUMPEN DE B 41539 30 1810 EN Instruction Manual OXYLIFT2...

Page 2: ...g of personnel All personnel involved with the operation servicing inspection and installation of the equipment must be suitably qualified for this work and must have studied the instruction manual in...

Page 3: ...o the plug this can cause malfunctions and damage Observe the operating voltage see the type plate No additional motor protection is required since the system has an integrated winding thermostat Inad...

Page 4: ...levered off The impeller can now be cleaned through the suction opening QUICKTIPSFORREMEDYING FAULTS Pump does not work Check mains current do not use a pin gauge Fuse faulty may be too weak please re...

Page 5: ...xylift 2 S kg 4 4 1 mm 15 P1 W 300 P2 W 200 U V 1 N PE 230 f Hz 50 I A 1 3 n min 1 2720 Leistung Performance Puissances H m 1 2 3 4 5 Q m h 8 7 6 4 2 Technische Daten Technical Data Caract ristiques t...

Page 6: ...d Oxylift 2 JP46921 Oxylift 2S JP46922 Leitung Cable 1 5 m JP46925 4 m JP46926 10 m JP45084 20 m JP46927 Schwimmer Float JP42771 Schaltwelle Shift shaft JP42770 Haube Top cover Oxylift 2 JP46928 Oxyli...

Page 7: ...ised standards FI Direktiivi Yhdenmukaistettu standardi FR Directives Normes harmonis es HU Ir nyelve Harmoniz szabv nyok IT Direttive Norme armonizzate NL Richtlijnen Geharmoniseerde normen PL Dyrekt...

Page 8: ...Pump Technical Services Limited Pump House Unit 12 Bilton Road Industrial Estate Erith Kent DA8 2AN Tel 01322 357 080 Fax 01322 341 341 Email sales pts jung co uk...

Reviews: