Penn F261 Series Product Bulletin Download Page 6

F261 Series Fluid Flow Switches Product Bulletin

6

Technical Specifications

 

 

 

 

Table 8:   F261xxH Series Standard Controls Electrical Ratings

Volts 50/60 Hz

UL60730/UL1059

EN60730

24

120

208

240

24

230

Horsepower

1

1

1

Full Load Amperes

16

10

10

8

Locked Rotor Amperes

96

60

60

48

Resistive Amperes

16

16

10

10

16

16

Pilot Duty VA

125

720

720

720

77

720

Table 9:  UL Conformity Declaration Information

Information

Description

Purpose of Control

F261 Fluid Flow Switch

Construction of Control

Electronic independently mounted control

Number of Cycles

100,000 cycles

Method of Mounting 
Control

Mounting to sensed media vessel/orientation

Type 1 or Type 2 Action

Type 1.C (Microinterruption)

External Pollution Situation 

Pollution degree 4

Internal Pollution Situation

Pollution degree 2

Rated Impulse Voltage

4,000 VAC

Ball Pressure Temperature

Enclosure:

 266°F (130°C )

Switch Component:

 252°F (122°C)

Control Adjustment 
Instruction

-

Field Wiring Rating

Wire/Cord Temperature Ratings:

• 

140°F (60°C) only permitted when ambient air and media are less than 
113°F (45°C)

• 

167°F (75°C) only permitted when ambient air and media are less than 140°F (60°C)

• 

194°F (90°C) only permitted when ambient air is less than 140°F (60°C) and media is less 
than 167°F (75°C)

• 

302°F (150°C) permitted when ambient air is less than 140°F (60°C) and media is less 
than 249°F (121°C)

Vessel Pressure

F261 Fluid Flow Switch:

 290 psi (20 Bar)

F261 Series Fluid Flow Switches (Part 1 of 2)

Switch

SPDT

Enclosure

UL: Type 3R or Type 4
CE: IP43 (IP23 with drain hole plug removed) or IP67

Wiring Connections

Three color-coded screw terminals and one ground terminal

Conduit Connection

One 7/8 in. (22 mm) hole for 1/2 in. trade size (or PG16) conduit

Pipe Connector

Standard: 1 in. 11-1/2 NPT Threads

Maximum Fluid Pressure

290 psi (20 bar)

Minimum Fluid Temperature

1

-20°F (-29°C)

Summary of Contents for F261 Series

Page 1: ...ype 4 NEMA Polycarbonate Enclosure Provides dust protection in indoor applications Suitable for Use in Other Environmental Air Space Plenums in accordance with Section 300 22 C of the National Electrical Code Viton Diaphragms Allow use in fluid lines carrying chlorinated water treated water or other nonhazardous fluids Low Flow Operation on Low Flow Models Actuates switch with less than 1 0 GPM 3 ...

Page 2: ... these models with pipes carrying fluids at temperatures in the range of 20 F to 250 F 29 C to 121 C A sealing O ring between the cover and case allows these models to be used in high humidity environments or applications where the fluid temperature is below the ambient dew point temperature Do not use these models in applications or environments where the temperature may cause the fluid to freeze...

Page 3: ... screw adjusts the rate of the flow required to activate the switch See Table 3 through Table 6 for flow rates Figure 2 Dimensions for F261 Standard Flow Switch in mm 1 2 12 Typical Thread Engagement 3 1 2 89 4 1 2 114 5 11 16 144 8 3 4 222 2 3 4 70 11 16 18 2 1 8 54 1 2 in trade size or PG 16 conduit opening FIG F261_stndrd_dmnsns 4 102 2 51 1 11 1 2 NPT 30 mm Hex 2 9 16 65 ...

Page 4: ...2 3 43 53 63 83 Minimum Adjustment Flow Increase Close R to Y 4 20 0 95 5 80 1 32 7 50 1 70 13 7 3 11 18 0 4 09 27 5 6 24 65 0 14 8 125 28 4 190 43 2 375 85 2 Flow Decrease Close R to B 2 50 0 57 3 70 0 84 5 00 1 14 9 50 2 16 12 5 2 84 19 0 4 32 50 0 11 4 101 22 9 158 35 9 320 72 7 Maximum Adjustment Flow Increase Close R to Y 8 80 2 0 13 3 3 02 19 2 4 36 29 0 6 59 34 5 7 84 53 0 12 0 128 29 1 245...

Page 5: ... Flow Decrease Close R to B 76 0 1 93 111 25 2 135 30 7 400 90 8 Table 5 Standard Flow Models Cross Reference F61 Series Model F261 Series Model F61KB 11C F261KAH V01C F61LB 1C F261MAH V01C F61MB 1C F261MAH V01C F61MB 5C F261MAH V01C Table 6 F261 Series Standard Model Flow Switches Product Code Number Description F261KAH V01C Standard model flow switch with Type 3R NEMA enclosure 1 in 2 in 3 in an...

Page 6: ...ge 4 000 VAC Ball Pressure Temperature Enclosure 266 F 130 C Switch Component 252 F 122 C Control Adjustment Instruction Field Wiring Rating Wire Cord Temperature Ratings 140 F 60 C only permitted when ambient air and media are less than 113 F 45 C 167 F 75 C only permitted when ambient air and media are less than 140 F 60 C 194 F 90 C only permitted when ambient air is less than 140 F 60 C and me...

Page 7: ... these specifications consult Johnson Controls PENN Refrigeration Application Engineering at 1 800 275 5676 Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products United States Emissions Compliance This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits ar...