Penn A421 Series Installation Manual Download Page 6

The purpose of this parameter is to prevent over-

cooling that could occur if a long Ont is used when

the outside air is very cold.

Note: 

If LtS is left at the default value (40°F), the Ltt

parameter has little or no impact.

Minimum Relay On-Time (Ont)

Select the minimum relay On-time per cycle period

(cP). Ont is used when the sensed temperature

is greater that the LtS. The range of values are 0

seconds to 300 seconds.
During any relay On-time (Ont or Ltt), Ont is

displayed followed by the remaining Ont seconds

and the sensed temperature in sequence. This

sequence of three screens continues until the Ont

seconds expire for the cP.
When the fan relay is On for a temperature (free-

cooling) ventilation cycle, the screen displays the

sensed temperature and a snowflake in the lower-

right corner of the screen to indicate the fan relay

is On for free-cooling.

Cycle Period (cP)

Select the Cycle Period for free-cooling and

ventilation control. The range of values are zero 0

minutes to 60 minutes.

Sensor Offset Adjustment (So)

Sensor offset allows you to compensate for any

difference between the displayed temperature

value and the temperature sensed at the A99

sensor. Select a temperature value to offset the

temperature displayed on the LCD from the

temperature sensed at the sensor. The sensor

offset adjustment range is from -5°F to 5°F or -3°C

to 3°C in 1° increments.

Sensor Failure mode (SF)

Select whether the control’s fan relay operates as

energized or de-energized in the event of a sensor

or sensor wiring failure. When the control detects

a sensor circuit failure, the fan relay operates in

the selected sensor failure mode. The LCD flashes

SF

 and 

OP

 if the sensor circuit is open or 

SF

 and 

SH

if the sensor circuit is shorted.

Backlight Brightness Level (bll)

The backlight brightness level feature allows

you to adjust the LCD backlight intensity. At level

0 the backlight is off. Level 10 is the brightest

backlight setting and the system default. The

selected backlight brightness level is applied

to the LCD during normal operation. When you

enter the programming menus to set up the

control or press any key, the LCD automatically

goes to the brightest level. If you do not press a

key for 30 seconds, the main screen is displayed

and the backlight setting returns to the selected

brightness level.

Switch-Activated Override (Ord)

When a switch is closed between BIN and COM

terminals of the TB3, the control is overridden, and

the fan relay remains on. The fan relay remains On

until the circuit (toggle switch) between BIN and

COM is open.
The relay remains energized regardless of the

sensor value, sensor fail state, or any timing

parameters (cP, Ont, Ltt). The control display

alternates between the main display and manual

override (Ord).

Table 3: Standard parameter setup codes, descriptions,

range of values, and default values

Parameter

code

Parameter

description (menu)

Range of

usable

values

1

Factory

default
value

1

Un

Temperature Units

(Advanced only)

ºF or ºC

ºF

LtS

Low Temperature Stop

(Advanced only)

-40ºF to

212ºF
(-40ºC to

100ºC)

40ºF

HtS

High Temperature Stop

(Advanced only)

-40ºF to

212ºF
(-40ºC to

100ºC)

212ºF

OFF

Relay Off Temperature

(Basic, Advanced, and

Restricted)

-40ºF to

212ºF
(-40ºC to

100ºC)

70ºF

On

Relay On Temperature

(Basic and Advanced)

-40ºF to

212ºF
(-40ºC to

100ºC)

75ºF

Ltt

Low Temperature On-

Time (Advanced only)

0 seconds to

300 seconds

60 seconds

Ont

Minimum Relay On-

Time (Advanced only)

0 seconds to

300 seconds

60 seconds

cP

Cycle Period

0 minutes to

60 minutes

10 minutes

So

Sensor Offset

Adjustment (Advanced)

-5ºF to 5ºF
(-3 to 3ºC)

0ºF

SF

Sensor Failure Action

(Basic and Advanced)

0 = output

relay de-

energized

1 = output

relay

energized

1 output

relay

energized

bll

LCD Backlight

Brightness Level

Adjustment (Advanced

only)

0 to 10; 0 =

backlight

off, 10 =

brightest

backlight

setting

10 (brightest

backlight)

1

The default values for general application models are shown.

OEM models may have different default values.

A421 Series Electronic Temperature Controls with Cycle Timer Installation Guide

6

Summary of Contents for A421 Series

Page 1: ...ou de protection en cas de d faillance ou de dysfonctionnement du A421 Control The A421 Series Electronic Temperature Controls are single stage electronic temperature controls with a single pole doubl...

Page 2: ...range of usable values from 40 F to 212 F or 40 C to 100 C See Wiring Technical specifications and refer to the A99B Series Temperature Sensors Product Technical Bulletin LIT 125186 for more informat...

Page 3: ...l ratings Exceeding the electrical ratings can result in permanent damage to the control and void any warranty Important Run all low voltage wiring and cables separate from all high voltage wiring It...

Page 4: ...re for 120 VAC supply power applications Connect the L1 supply power lead for all 208 240 VAC supply power applications 120V Line voltage 120 VAC control power hot Connect the 120 VAC supply power hot...

Page 5: ...On temperature On Select the temperature at which the output relay energizes the LC to LNO relay contacts close cut in and the green LED lights The range of usable temperature values is 40 F to 212 F...

Page 6: ...brightest backlight setting and the system default The selected backlight brightness level is applied to the LCD during normal operation When you enter the programming menus to set up the control or p...

Page 7: ...ave a new value the control reverts to the last saved value After 30 seconds of inactivity while in any screen the control reverts to the Main screen Basic menu Use the Basic menu to quickly edit the...

Page 8: ...tween the On and OFF values the following behavior is enforced The fan relay is On for at least the Minimum Relay On Time Ont during a Cycle Period cP See Figure 8 The fan relay goes Off when the sens...

Page 9: ...Restricted mode prevents casual users from over adjusting the control in your application or from inadvertently changing the mode of operation from cooling to heating or heating to cooling by over adj...

Page 10: ...e See Troubleshooting procedure Cycle power to reset the control SF flashing alternately with SH Shorted temperature sensor or sensor wiring Output functions according to the selected SF mode See Trou...

Page 11: ...with Cycle Timer Type 1 NEMA IP20 standard enclosure for DIN rail and surface mount applications Rated for 120 240 VAC Includes timer for On Off duty cycle control Includes an A99BB 200C temperature s...

Page 12: ...Specification Description Power consumption 1 8 VA maximum Supply power 110 120 or 208 230 240 VAC 50 60 Hz Table 8 A421 Series Electronic Temperature Controls Technical Specifications Specification...

Page 13: ...00 RH condensing Shipping weight 1 4 oz 41 g for 6 1 2 ft 2 m sensor Accessories See Table 7 1 When any A99 Series Temperature Sensor is connected to a standard A421 Control model the range of display...

Page 14: ...SON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact information refer to www johnsoncontrols com locations 2019 Johnson Controls Al...

Reviews: