Penn A421 Series Installation Manual Download Page 5

Setup and adjustments

The front panel of the A421 Series Electronic Temperature

Control has an LCD and a three-button UI as shown in the

following figure.

Figure 5: A421 Control front panel with LCD and three-

button UI

LCD

The A421 Series Control has a backlit LCD screen (Figure

5). You can adjust the LCD brightness. During normal

operation, the LCD displays the Main screen, which

provides following information:
• Temperature sensed at the A99 sensor

• Selected temperature units (°F or °C)

• Mode of operation (snowflake = cooling mode only)

• Binary Input status (BIN) when a user-supplied toggle

switch is connected and closed to manually override the

relay control.

During setup and adjustment, the LCD displays the

parameter code screens and the parameter value screens.

See the 

A421 Control parameter setup menus

 for more

information.

Three-button touchpad

The touchpad has three buttons for setup and adjustment

of the A421 Control (Figure 5). See 

Navigating the Basic

and Advanced menus

 for more information on using the

three-button touchpad.

Relay status LED

The green LED on the front panel illuminates when the

SPDT output relay is energized and the LC and LNO

contacts are closed. See Figure 5.

Parameter codes and modes of

operation

Relay Off temperature (OFF)

Select the temperature at which the output relay

de-energizes, the LC to LNO relay contacts open

(cutout), and the green LED goes off. The range

of usable temperature values is -40°F to 212°F or

-40°C to 100°C in 1° increments.

Relay On temperature (On)

Select the temperature at which the output relay

energizes, the LC to LNO relay contacts close (cut

in), and the green LED lights. The range of usable

temperature values is -40°F to 212°F or -40°C to

100°C in 1° increments.
The A421 Series Control with Cycle Timer functions

in Cooling Mode only.

Temperature Units (Un)

Select the preferred temperature scale for your

application. Select either the Fahrenheit (°F) or

Celsius (°C) temperature scale.

Note: 

After changing the value for the temperature

units (Un), confirm that the temperature values for

the other parameter codes are still correct for your

application.

Low Temperature Stop (LtS)

Select the lowest temperature value below

which the Low Temperature On-Time (Ltt) is

enforced. This parameter is also used when

control adjustment is restricted. See 

Restricting

user adjustment

.

The range of usable temperature values is -40°F to

212°F or -40°C to 100°C in 1° increments.

High Temperature Stop (HtS)

Select the highest temperature value in which the

On/OFF control band can be adjusted when the

control adjustment is restricted. See 

Restricting

user adjustment

.

The range of usable temperature values is -40°F to

212°F or -40°C to 100°C in 1° increments.

Restricted Adjustment mode

The HtS and LtS values define the restricted

adjustment temperature range and are enforced

only when the A421 Control is set to the restricted

adjustment mode (Figure 9). See 

Restricting user

adjustment

.

Low Temperature On-Time (Ltt)

Select the minimum relay On-time whenever the

sensed temperature is less than the LtS. The range

of values are 0 seconds to 300 seconds.

A421 Series Electronic Temperature Controls with Cycle Timer Installation Guide

5

Summary of Contents for A421 Series

Page 1: ...ou de protection en cas de d faillance ou de dysfonctionnement du A421 Control The A421 Series Electronic Temperature Controls are single stage electronic temperature controls with a single pole doubl...

Page 2: ...range of usable values from 40 F to 212 F or 40 C to 100 C See Wiring Technical specifications and refer to the A99B Series Temperature Sensors Product Technical Bulletin LIT 125186 for more informat...

Page 3: ...l ratings Exceeding the electrical ratings can result in permanent damage to the control and void any warranty Important Run all low voltage wiring and cables separate from all high voltage wiring It...

Page 4: ...re for 120 VAC supply power applications Connect the L1 supply power lead for all 208 240 VAC supply power applications 120V Line voltage 120 VAC control power hot Connect the 120 VAC supply power hot...

Page 5: ...On temperature On Select the temperature at which the output relay energizes the LC to LNO relay contacts close cut in and the green LED lights The range of usable temperature values is 40 F to 212 F...

Page 6: ...brightest backlight setting and the system default The selected backlight brightness level is applied to the LCD during normal operation When you enter the programming menus to set up the control or p...

Page 7: ...ave a new value the control reverts to the last saved value After 30 seconds of inactivity while in any screen the control reverts to the Main screen Basic menu Use the Basic menu to quickly edit the...

Page 8: ...tween the On and OFF values the following behavior is enforced The fan relay is On for at least the Minimum Relay On Time Ont during a Cycle Period cP See Figure 8 The fan relay goes Off when the sens...

Page 9: ...Restricted mode prevents casual users from over adjusting the control in your application or from inadvertently changing the mode of operation from cooling to heating or heating to cooling by over adj...

Page 10: ...e See Troubleshooting procedure Cycle power to reset the control SF flashing alternately with SH Shorted temperature sensor or sensor wiring Output functions according to the selected SF mode See Trou...

Page 11: ...with Cycle Timer Type 1 NEMA IP20 standard enclosure for DIN rail and surface mount applications Rated for 120 240 VAC Includes timer for On Off duty cycle control Includes an A99BB 200C temperature s...

Page 12: ...Specification Description Power consumption 1 8 VA maximum Supply power 110 120 or 208 230 240 VAC 50 60 Hz Table 8 A421 Series Electronic Temperature Controls Technical Specifications Specification...

Page 13: ...00 RH condensing Shipping weight 1 4 oz 41 g for 6 1 2 ft 2 m sensor Accessories See Table 7 1 When any A99 Series Temperature Sensor is connected to a standard A421 Control model the range of display...

Page 14: ...SON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact information refer to www johnsoncontrols com locations 2019 Johnson Controls Al...

Reviews: