HVAC Signals
Y, Y2, G, W, W2, O/B 24VAC – Industry standard 24VAC signal
outputs directly control up to 2 stages of Heat and 2 stages Cool
for both Conventional and Heat Pump systems. Auxiliary and
Emergency Heat are also supported.
Economizer Signals
ACT 0-10 VDC Actuator Output – This signal modulates the
damper actuator.
POS 0-10 VDC Actuator Position Input – This signal tracks
damper position.
ENA 24 VAC Enable Output – This signal energizes when the
Economizer is active and can be used to control exhaust fans or
auxiliary economizer equipment.
Variable Speed Fan Signals
AUX 0-10 VDC Speed Output – This signal adjusts the speed
of the fan.
G
24 VAC fan start/stop signal.
Temperature Sensors
SAT
10K type 2 input for Supply Temperature
RAT
10K type 2 input for Return Temperature
OAT 10K type 2 input for Outside Air Temperature
Supplied Accessories
(3) 10K type 2 temperature sensors – 1% accuracy with 0.1 °F
resolution
(1) Outside Air Sensor Mount – insulated intake hood mount
Thermostat Inputs
Integrated Room Temperature Sensor: -20 °F – 128 °F with
0.1 °F resolution (Model TS200)
Integrated CO2 sensor: 0 – 2000 ppm +/- 50 ppm accuracy,
1 ppm resolution (Model TS250)
Integrated Humidity sensor: 0 – 100% RH (Model TS200H or
TS250H)
Supplied Online Data
Outside Relative Humidity - local humidity levels based on
installation location zip code.
Barometric Pressure - local barometric pressure levels based
on installation location zip code
Optional Accessories
TA1 – wired sensor: -20 °F – 128 °F with 0.1 °F resolution or
input for dry contact Occupancy sensor
RT1 – wireless remote sensors: -20 °F – 128 °F with 0.1 °F
resolution
PRX1 - wireless input for dry contact Occupancy sensor