GB - 1
PEHA_M_940_24_JRM (Rev05_130215)
126098-04
PEHA Elektro GmbH & Co. KG
Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: [email protected] • Internet: www.peha.de
coDIng swITch
The output module‘s address is set by the coding switch built into the PHC control
module. The setting of the coding switch is presented in the PHC software under the
menu item „
Components
g
Edit Modules
“.
Make sure that no identical module addresses are given for PHC output modules.
The setting of the coding switch may be carried out by technicians only. For this the
PHC module needs to be switched off and it must be ensured that there can be no
electrical discharge.
currenT consumPTIon
To calculate the current consumption for the power supply, you should assume a
consumption of 60 mA (internal consumption 10 mA, per relay 6 mA). When a relay
is switched on the current increases to 120 mA for about 2 seconds.
TechnIcaL DaTa
Power supply
Phc system (Phc bus)
Nom. 24 V DC
21-28 V DC (ripple voltage 5 %)
own consumption
10-60 mA
In-/output module bus
2 modular sockets 6-pin (PHC bus)
external voltage
(Terminal I0+, I0-, I1+, I1-)
4 terminal clamps for the connection of 2 external
power supplys (12-24V DC)
relay outputs
(Terminal O0-O3)
8 outputs (O0-O3) in 4 groups with 2 terminals
clamps (+ and -) for loads up to 1 A (12-24V DC)
Life-time cycle of relays
50,000 switchings with max. load
coding
DIP switch, 5-pin (Module address)
ambient temperature
+10° to +50°C
storage temperature
-20° to +60°C
screw terminals
max. 2 x 1,5 mm²
Test specifications
EN 60669-2-1
approbationen
CE KEMA/KEUR CEBEC
Protection level
IP20
Dimensions
width = 72 mm
height = 55 mm
PermITTeD LoaDs For The reLay ouTPuTs
Type of load connected
max. output load per output
Motor load
1 A
warranTy conDITIons
These operating instructions are an integral part of both the device and our terms of
warranty. They must be handed over to the user. The technical design of the appliance
is subject to change without prior notification.
PEHA
products are manufactured
and quality-checked with the latest technology according to applicable national and
international regulations. Nevertheless, if a product should exhibit a defect,
PEHA
warrants to make remedy as follows (regardless of any claims against the dealer to
which the end user may be entitled as a result of the sales transaction):
In the event of a justified and properly established claim,
PEHA
shall exercise its
prerogative to either repair or replace the defective device. Further claims or liability
for consequential damage are explicitly excluded. A justifiable deficiency is deemed to
exist if the device exhibits a structural, manufacturing, or material defect that makes it
unusable or substantially impairs its utility at the time it is turned over to the end user.
The warranty does not apply to natural wear, improper usage, incorrect connection,
device tampering or the effects of external influences. The warranty period is 24 months
from the date of purchase by the end user from a dealer and ends not later than 36
months after the device’s date of manufacture. German law shall be applicable for the
settlement of warranty claims.
DIsPosaL oF The DevIce
Do not dispose of old devices in the household waste! The device must be
disposed of in compliance with the laws and standards of the country in which it
is operated! The device contains electrical components that must be disposed
of as electronics waste. The enclosure is made from recyclable plastic.
DescrIPTIon
The PHC output module 940/24 JRM can control four blinds or roller shutters by
the outputs
(o0-o3)
. The module features within the PHC software four separate
channels for time measurement that can be used independently from the blind/roller
shutter functions as virtual outputs. One channel for time measurement is used for
example under the point
„sun sensor delay time measurement“
in the roller shutters/
blinds group tools for clocking the sun delay.
The module is divided into 4 groups and features 2 inputs to connect 2 external power
supplys
(12-24V DC)
. The upper terminal clamps
(
I
0+,
I
0-)
supplies the upper 2 output
groups
(o0-o1)
with the applied power supply and the lower terminal clamps
(
I
1+,
I
1-)
supplies the lower 2 output groups
(o2-o3)
.
The module switches the external
positive voltage to one of the motor connections used
(o0+ to o3+)
for raising or
lowering of a blind or roller shutter. In idle state the motors are connected by the motor
connections
(o0- to o3-)
with the earth (GND).
connecTIon DIagram
safety recommendation!
During a reset of the PHC system
(e.g. after an interruption of the power
supply) all relay outputs are in home
position (idle state).
Since all motor connections
(o0- to
o3-)
are connected to earth (GND) in
idle state it needs to be ensured that
the earth (GND) of the external power
supply is connected to the terminal
clamps
I
0-
and
I
1-
.
m
m
+ -
External
Voltage
(12 - 24V DC)
externe
spannung
(12 - 24v Dc)
m
m
+ -
External
Voltage
(12 - 24V DC)
V1+ V1- V1+ V1-
V1+ V1-
V1+ V1-
V1+
V1-
O0+
O2+
O0-
O2-
O1+
O3+
O1-
O3-
0+
I
1+
I
0-
I
1-
I
V0+ V0- V0+ V0-
V0+ V0-
V0+ V0-
V0+
V0-
M0
M2
M3
M1
940/24 JRM
PHC System
1A/12-24V DC (I
N
max 4x1A)
M
M
coding switch
module address
mounTIng
The installation of the PHC modules may be carried out by authorised technicians only.
During installation the system‘s electricity has to be switched off. The PHC module is
designed for mounting on a 35mm top hat rail acc. EN 50022 in in-/on-wall distribution
housing. The devices can be mounted directly next to each other.
attention!!
The PHC modules may
not
be employed in connection with devices that
may endanger people, animals or property when operated.
The following points must be observed:
- the valid laws, standards and regulations
- the technical state of the art during installation
- the PHC manual and the operating instructions of the PHC modules.
- the fact that operating instructions can only cover general regulations and that
these regulations must be considered in the context of the PHC system.
The following systems may not be switched by Phc modules:
- safety switches such as EMERGENCY OFF
- emergency power supplies
- fire alarm systems
- emergency lighting systems
DaTa connecTIon
The connection between PHC control unit and other PHC modules is established by
the PHC bus line and the modular connectors of the modules. The module connectors
are switched parallel in the modules (except in the PHC power supply unit) and
therefore freely selectable as in- or output. Thus the PHC module can be positioned
anywhere in the data line.
A PHC bus line of 30 cm length is included with every PHC module. It is needed for
connecting a neighbouring module or for connecting a module in the next distributor
row. The modules are supplied with voltage by the bus line. Power needs to be
switched off before disconnecting the bus line.
InsTaLLaTIon anD oPeraTIng InsTrucTIons
Phc output modul 940/24 Jrm for blinds and roller shutters
8 outputs (2x 4x 1 a) for 4 Dc motors from 12 to 24v
940/24 Jrm
gb