NECTOR
Page
21
OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
d7
Dripping duration
(minutes)
At the end of defrosting, the compressor and fans remain
stationary for the set time d7, the defrosting LED on the front
of the panel flashes.
0 ÷ 10 min
0 = disabled
0 min
F5
Fan pause
after defrosting (minutes).
Allows the fans to remain stationary for a time F5 after
dripping. This time is counted from the end of the dripping. If
the dripping is not set, at the end of defrosting the fans pause
immediately.
0 ÷ 10 min
0 = disabled
0 min
A1
Minimum temperature alarm
It is used to define a minimum temperature value for the
environment to be chilled. Below the A1 value, the alarm
status will be signalled with the alarm LED flashing, the
temperature displayed flashing and an internal buzzer
acoustically signals the existence of the anomaly.
-45.0 ÷ A2 °C
-45.0°C
A2
Maximum temperature alarm
It is used to define a maximum temperature value for the
environment to be chilled. Above the A2 value, the alarm
status will be signalled with the alarm LED flashing, the
temperature displayed flashing and an internal buzzer
acoustically signals the existence of the anomaly.
A1 ÷ 99.0 °C
+99.0°C
dFr
Enable real-time defrosting
With d0=0 and dFr=1 it is possible to set up to 6 real-time
defrosts over a day through the dF1…dF6 parameters.
0 = Disabled
1 = Enabled
0
dF1
…
dF6
Defrost schedule
You can set up to 6 times for defrost.
00:00 ÷ 23:59
00:00
tdS
Start of day phase
(not used if In1…In7 = 8 or -8)
00:00 ÷ 23:59
06:00
tdE
End of day phase
(not used if In1…In7 = 8 or -8)
00:00 ÷ 23:59
22:00