background image

 

 

nano LINE

 

200NDIN4CK01
**

 

 

PEGO S.r.l. 

Via Piacentina, 6/b - 45030 -  ROVIGO 

Tel : +39(0)425 762906 - Fax: +39(0)425 762905 

www.pego.it   -  e-mail: [email protected] 

 

200NDIN4CK01_02-19_ITA_ENG  #  Rev.02-19  #  03/07/2019

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

THERMOSTAT FUNCTION MODES (mOd) 

The  variable  mOd  allows  the  selection  of  function  mode  of  the 

thermostat, in particular: 

 

- COLD MODE (mOd=0) 

The DO1 output is activated  when  the  temperature  measured  by 

the ambient probe reaches or exceeds the SET POINT+r0 value and 

remains active until the temperature drops below the SET POINT. In 

this mode, the DO1 output is linked to the cold function icon. 

dO3/dO4  can  be  configured  as  hot  relay  for  neutral  zone 

management.  The  output  is  activated  when  the  ambient 

temperature  is  lower  than  SET  POINT-r0  and  remains  active  until 

the temperature exceeds the SET POINT. 

 

- HOT MODE (mOd=1) 

The DO1 output is activated  when  the  temperature  measured  by 

the ambient probe reaches or exceeds the SET POINT-r0 value and 

remains active until the temperature increases and exceeds the SET 

POINT. In this mode, the DO1 output is linked to the hot function 

icon; defrosting and fan stop FSt are DISABLED.

 

 

 

PASSWORD FUNCTION

 

The password function is activated by entering a value other than 0 

for  the  PA  parameter.  See  parameter  P1  for  various  protection 

levels.  The  protection  is  activated  automatically  if  the  keyboard 

remains inactive for about 30 seconds. The figure 000 appears on 

the display. Use the up/down keys to change the number and the 

SET key to confirm. The password entry template 000 disappears if 

the keyboard is not activated within 30 seconds. If you forget the 

password, use the universal number 100. 

 

EMERGENCY MODE IN THE CASE OF ERROR EO

 

This  safety  mode  guarantees  the  functioning  of  the  compressor 

even  in  the  case  of  a  faulty  ambient  probe  (error  EO).  If  probe 

errors  E0  and  CE1  are  different  to  0,  the  compressor  functions  in 

operation pause mode, with compressor ON for the time CE1 and 

OFF for the time CE2. If CE1>0 in the case of error E0, defrosting is 

performed  in  normal  functioning  mode.  If  CE1=0  the  emergency 

mode in the presence of error E0 remains disabled. The compressor 

remains off and defrosting is prevented to conserve the remaining 

cold.  Eliminate  as  soon  as  possible  the  cause  of  error  E0  and 

reactivate the control’s normal function for a correct temperature 

adjustment. 

 

MANUAL DEFROSTING ACTIVATION

 

To activate defrosting simply press the DOWN key for more than 30 

seconds;  this  activates  the  heating  elements  relay.  Defrosting  is  not 

activated  if  the  appropriate  conditions  are  not  present  (end-of-

defrosting temperature (d21 or d22) set lower than the temperature 

read by the evaporator probe). Defrosting terminates when the end-

of defrosting temperature (d21 or d22) is reached or for a maximum 

defrosting time (d31 or d32) or by manually forced end-of-defrosting 

(end-of-defrosting key or digital input). 

 

 

Once  the  reset  occurred,  a  BIP  with  the  buzzer  is  provided  to 
confirm  the  occurred  cancelation.  To  exit  the  menu,  wait  10 
seconds without pressing anything or press simultaneously the 
up and down arrows. 
HACCP variables are available in read-only mode and are the 
following: 

VARIABLE LIST HACCP LEVEL  

(Values in read-only) 

E## 

Indicates the latest 

activated 

temperature alarm. 

EH = high temperature alarm  
EL = low temperature alarm 
-- = no alarms have been 
activated from the latest 
reset 

### 

Temperature peak 

value reached during 

the latest EH or EL 

alarm 

-

45…+45°C

 

--- = no alarms have been 
activated from the latest 
reset 

y## 

Year of the start of 

the last temperature 

alarm 

y 00 

 y99 

y -- = no alarms have been 
activated from the latest 
reset 

M## 

Month of the start of 

the last temperature 

alarm 

M 01 

 M12 

M -- = no alarms have been 
activated from the latest 
reset 

d## 

Day of the start of the 

last temperature 

alarm 

d 01 

 d31 

d -- = nessun allarme 

intervenuto dall’ultimo reset

 

h## 

Hour of the start of 

the last temperature 

alarm 

h 00 

 h24 

h -- = no alarms have been 
activated from the latest 
reset 

m## 

Minutes of the start 

of the last 

temperature alarm 

m 00 

 m59 

m -- = no alarms have been 

activated from the latest 

reset 

t## 

Duration (hours) of 

the latest 

temperature alarm 

t 00 

 t99 

t -- = no alarms have been 

activated from the latest 

reset 

C## 

Counter of the nr of 

temperature alarm 

events occurred (being 

memorized data of the 

latest  temperature 

alarm event, the counter 

is boosted to know if 

previously other alarms 

occurred. This counter 

resets with the 

memorized alarm reset 

(silenced  SET for 

5 sec). It is implemented 

at every new 

temperature alarm). 

C 00 

 C99 

C -- = no alarms have been 

activated from the latest 

reset 

 

DIAGNOSTICS 

The  display  shows  ‘orH’  for  temperature  ou

t  of  range 

greater than +99.9°C. It shows 

‘orL’ for temperature out of 

range less than -45.0°C. 

In the case of faults, the “Expert nano” control unit informs the 

operator by means of alarm codes shown on the display and an 

acoustic  signal emitted  by  the  buzzer (if  present).  The  acoustic 

alarm  can  be  stopped  by  pressing  the  UP  key  (the  error  code 

remains) and can be reactivated by pressing the SET key. In the 

event of an alarm, one of the following messages is displayed: 

 

ALARM CODE TABLE 

Var 

MEANING 

E0

 

Functional fault of ambient probe. 

Eu1 

Functional fault of defrosting probe (in this case, any defrosting 

processes will have a duration equal to time d31). 

Eu2 

Functional fault of defrosting probe (in this case, any defrosting 

processes will have a duration equal to time d32). 

E2 

EEPROM memory error.  All outputs are deactivated except for 

alarm outputs if present. 

E8 

Man-in-room alarm. 

Ec 

Compressor protection alarm (e.g. thermal protection or max. 

pressure  switch).  All  outputs  are  deactivated  except  for  the 

alarm output if present. 

Ed 

Door open  alarm.  When  the  door  switch  opens  and  the  tdo 

time  has  elapsed,  normal  function  of  the  control  is  reset, 

triggering the door open alarm (Ed). 

EL 

Minimum  temperature  alarm.  The  letters  EL  flash  alternating 

with the temperature (see parameter A1). 

EH 

Maximum temperature alarm. The letters EH flash alternating 

with the temperature (see parameter A2). 

E9 

Room  light  alarm.  The  letters  E9  flash  alternating  with  the 

temperature (see parameter  dO3 and Tdo). 

E6 

Clock failure alarm. 

En 

Communication  error  between  the  ECHO  display  and  the 

Master 

 

 

MANUALLY FORCED END OF CURRENT DEFROSTING

 

Pressing  the  DOWN  key  for  3  seconds  during  defrosting  forces 

the end of the current defrosting. In the case of manual end-of-

defrosting, dripping is also excluded. 

 

HOT GAS DEFROSTING 

Set the parameter  d1 = 1 or 2 for the management of inversion 

defrost  cycle.  During  the  entire  defrosting  process  the 

compressor and defrost relays are activated. In this case, you can 

not set defrost in succession, dd2 is forced to 0. During dripping 

(d7)  the  compressor  stops  and,  if  d1  =  2,  the  defrost  relays 

remain  activated    in  order  to  ensure  the  ignition  of  the 

resistances  of  the  basins.  If  d1  =  2  it  may  be  necessary  to  add 

external  electromechanical  components  for  proper  control  of 

the solenoid valves. 

For  a  correct  control  of  the  system,  the  installer  must  use  the 

defrost  output  which  must  allow  the  opening  of  the  inversion 

cycle  electrovalve  and  closing  of  the  liquid  electrovalve.  For 

capillary  systems  (without  thermostatic  valve)  it  is  sufficient  to 

control  the  inversion  cycle  electrovalve  using  the  defrost  relay 

command. 

 

HEATER DEFROST BY TIME WITH TEMPERATURE CONTROL 

Set the parameter  d1 = 3 for the management of heater defrost 

by time with temperature control. During the defrost the outputs 

are  activated  when  the  evaporator’s  temperatures  are  lower 

than d21 or d22. Defrost stops after d31 or d32 minutes. It allows  

energy saving and a better defrost process. 

 

AMBIENT  TEMPERATURE  DISPLAY  DURING  AND  AFTER 

DEFROSTING 

During  defrosting  and  for a  minute following  the 

end  of  defrosting,  the  display  continues  to  display  the  last 

ambient temperature value read before start of defrosting.

   

 

RS-485 CONNECTION

 

Connection  to  a  RS485  network  must  be  chain  type,  avoiding 

star connections and observing A and B polarity. It is advisable 

to use BELDEN 8762 cables. The configuration of the device in 

the  TeleNET  program  is  performed  by  entering  the  module 

name such as “

Expert Nano4CK rel 3 or higher

” and assigning to 

it the same network address entered in the variable Ad. For a 

Modbus-RTU  network  connection  and  for  details  on  the 

protoco

ls  of  these  devices,  refer  to  the  manual  “

MODBUS-

RTU_EXP_DIN_NANO4CK

” which can be downloaded from our 

internet site at www.pego.it. 

 

HACCP ALARM MANAGEMENT 

With ambient probe temperature ≤ A1 , after the Ald time, the 

EL low temperature alarm is activated.  

With ambient probe temperature ≥ A2 , after the Ald time, the 

EH high temperature alarm is activated.  

During a  high or  low temperature  alarm,  the  display alternates 

the visualisation of the temperature with the EH or EL headings; 

the alarm relay is activated (if set), the Buzzer (silenceable) and 

the alarm bell icon (flashing).  

When  the  set  alarm  conditions  are  turned  off,  alarm  signals 

automatically undo (the alarm relay is deactivated, the buzzer is 

silenced and the normal visualisation is reactivated). 

The  alarm  bell  icon  remains  on  (fix)  to  indicate  that  EH  or  EL 

alarm  was  triggered  and  the  memorisation  of  the  event  (see 

HACCP  menu  for  displaying  the  latest  temperature  alarm 

activated).To get the alarm, push the arrow button up when the 

fix bell light is on.

 

Besides, the starting date of the latest EH or EL 

event is registered, together with its duration and its maximum 

or minimum reached temperature. 

A  counter  of  the  nr  of  occurred  alarms  from  the  latest  alarm 

reset (max 99 alarms can be counted) is also present.

 

To display data related to the latest temperature alarm, enter in 

the  HACCP  menu  (push  the  arrow  button  up  +  stand-by  for  3 

seconds). Inside the menu, all the data can be scrolled with the 

up  and  down  arrows or  they can  be  reset,  by  pressing  the SET 

 arrow up button for 5 seconds.  

 

 

E N G L I S H

 

 

ELECTRICAL CONNECTIONS 

1 - 2 

Power supply 

3 - 4 

DO4 Output (Default = room light) 

5 - 6 

Compressor Output  

7 - 8 

Fan Output 

9 - 10 

DO3 Output (Default =Defrost 1) 

15 - 16  RS485  15-B  16-A 
17 - 18  Digital Input 1 
19 

 20     Evaporator probe 2 / Digital Input 2 

21 - 22  Evaporator Probe 1 
23 - 24  Ambient Probe 
J2 

Display ECHO

 

NOTE : 

On

 the electronic board, the jumpers are 

already configured for the correct reading of 
the inputs. 
Their setting must not be changed. 

 
J11=1-2 

J21=1-2       J31=1-2          

J12=1-2 

J22=1-2 

  J32=1-2          

J13=open  J23=open     J33=open          

 

Summary of Contents for Expert DIN NANO 4CK

Page 1: ...VOTTLXDISPLAY ECHONANO Lunghezza 2 5m 200NANOTTL02 DISPLAYRIPETITOREDITEMPERATURAECHO ITALIANO Tensione di alimentazione Modello 200NDIN4CK01 230V 10 15 50 60Hz Potenza assorbita 5VA Max Condizioni cl...

Page 2: ...ementato solo se il compressore acceso e la temperatura dell evaporatore pi freddo inferiore a dSt 1 C1 Tempo minimo tra lo spegnimento e la successiva Accensione del compressore Range 0 15 min 0 CE1...

Page 3: ...ore rimane e viene riattivato con la pressione del tasto SET FORZATURA MANUALE DI FINE SBRINAMENTO IN CORSO Durante uno sbrinamento la pressione del tasto DOWN per 3 secondi forza la fine dello sbrina...

Page 4: ...lepossibiliinesattezzecontenutenelpresentemanuale sedovuteaderroridistampaoditrascrizionee si riservaildirittodiapportareaipropriprodottiquellemodifichecheriterr necessarieoutili senzapregiudicarnelec...

Page 5: ...B L2 5 Connection cable for temperature repeater ECHO Length 2 5m 200NANOTTL02 TemperaturerepeaterDisplay ECHO ENGLISH Power voltage Model 200NDIN4CK01 230V 10 15 50 60Hz Absorbed power 5VA Max Enviro...

Page 6: ...han dSt 1 C1 Minimum time between each turning off and on of the compressor Range 0 15 min 0 CE1 Duration of compressor ON time in the case of faulty ambient probe emergency mode Range 0 240min 0 Disa...

Page 7: ...messages is displayed ALARM CODE TABLE Var MEANING E0 Functionalfaultofambientprobe Eu1 Functional fault of defrosting probe in this case any defrosting processeswillhaveadurationequaltotimed31 Eu2 F...

Page 8: ...s of the device PEGO S r l does notaccept responsibility for any inaccuracies which may be present in this manual inthe case that these are due to printing or transcription errors and reservestheright...

Reviews: