TECHNICAL CHARACTERISTICS
ECP300 EXPERT U VD 6
ECP300 EXPERT U VD 12
Box dimensions
400x300x135 mm
400x300x135 mm
Weight
9 Kg
10 Kg
Protection rating
IP65
IP65
Power supply (3F+N+T)
400Vac ±10% 50/60Hz
400Vac ±10% 50/60Hz
Type of electric load
3-phase
3-phase
Working temperature
- 5 ÷ + 40 °C
- 5 ÷ + 40 °C
Storage temperature
-25 ÷ +55 °C
-25 ÷ +55 °C
Relative ambient humidity
From 30% to 95% RH w/out
condensate
From 30% to 95% RH w/out
condensate
Main switch / general protection
Interruption power
4 poles magnetothermic
16A
“D”
Icn=6kA / Ics=8kA / Icu=15kA
4 poles magnetothermic
25A
“D”
Icn=6kA / Ics=8kA / Icu=15kA
Dedicated protection for cell light
Differential magnetothermic circuit
breaker Id=30mA
Differential magnetothermic circuit
breaker Id=30mA
Control
PEGO
PEGO
Defrosting
Electrical
Electrical
Status indicators
LED + display
LED + display
Alarm signals
LED + Buzzer
LED + Buzzer
INPUTS
Ambient probe
NTC 10K 1%
NTC 10K 1%
Evaporator probe
NTC 10K 1%
NTC 10K 1%
Door switch
Present
Present
Man in cold-room alarm
Available
Available
OUTPUTS
Evaporator fans
500W (1ph)
2000W (1ph / 3ph)
Defrosting heaters
6000W (AC1) eq. resistive load
12000W (AC1) eq. resistive load
Room light
800W (AC1) resistive load
1200W (AC1) resistive load
Solenoid valve
Present
Present
Enable condensing unit
Present
Present
Aux1
100W
100W
Aux2
100W
100W
Door heater
Present
Present
Supervision system
TeleNET or Modbus
TeleNET or Modbus
CHAP. 2 - Technical characteristics