TROUBLESHOOTING
In the event of any anomalies the
ECP202 EXPERT D7.5
in case of anomalies, it notifies the
operator by means of the alarm codes displayed on the display and an audible signal emitted by a
buzzer inside the control panel. The EL and EH temperature alarms remain visible even after their
return (alarm icon lights on) until their acquisition (by pressing the key tacit). If an alarm condition
occurs, one of the following messages will be displayed on the display:
ALARM
CODE
POSSIBLE CAUSE
SOLUTION
E0
Cold room temperature sensor not working properly
•
Check that cold room temperature
sensor is working properly
•
If the problem persists replace the
sensor
E1
Defrost sensor not working properly
(In this case defrosts will last time d3)
•
Check that defrost sensor is
working properly
•
If the problems persists replace
the sensor
E2
Eeprom alarm
An EEPROM memory alarm has been detected
(All outputs except the alarm one are deactivated)
•
Switch unit off and back on
E8
Man in cold room alarm
•
Reset the alarm input inside the
cold room
Ec
Compressor protection tripped
(e.g. thermal protection or max pressure switch)
(All outputs except the alarm one
– where applicable
– are deactivated)
•
Check that compressor is working
properly
•
Check compressor absorption
•
If the problem persists contact the
technical assistance service
Ed
Open door Alarm. When the door is opened and after
tdo time, it’s setted back the normal functioning
giving door open alarm (Ed)
•
Check door switch status
•
Check door switch connections
•
If the problem persists contact the
technical assistance service
E9
Cell light alarm.
The light of the cell has been on for a time greater
than tdo.
•
Turn off the light
EH
Maximum temperature alarm.
The temperature inside the cold room has exceeded
the max. temperature alarm setting (see variables
A2, user programming level)
•
Check that the compressor is
working properly.
•
Sensor not reading temperature
properly or compressor start/stop
control not working.
EL
Minimum temperature alarm.
The temperature inside the cold room has exceeded
the min. temperature alarm setting (see variables A1,
user programming level)
•
Check that the compressor is
working properly.
•
Sensor not reading temperature
properly or compressor start/stop
control not working.
CHAPTER 7: TROUBLESHOOTING