Boiler Control Instruction & Operation Manual, Rev 1
Page
29
of 64
Setup & Tuning
Manual Operation
The Firing rate may be adjusted manually using the Operation screen. The user may adjust firing rate
anywhere between minimum rpm and maximum rpm.
Figure 17: Operation Screens
Auto/Manual
After selecting Manual Mode the User may adjust
modulation manually.
Rate
Select Manual modulation to enable user adjustment of
firing rate. The factory default is Automatic mode.
CH and DHW
The setpoint manual rates for each demand type can be
adjusted independently.
Service Trend
Access the trends on the Analysis screen (Home Screen >
Details > Analysis). Pick the variables you want to view
trends of from the drop-down box, and press Add. Press
the green Start Trending button. Press View to see a
graph of all trending variables.
Manual Pump Exercise
Allows the pumps to be set to either ON or Automatic.
When ON is selected pump will run. When Automatic is
selected, pump will follow settings assigned in Pump
Configure Menu.
NOTE:
Manual control mode locks firing rate to a fixed speed. The control stays in manual even through a power
cycle. Select Automatic when commissioning is complete.