Peco TH170 User Manual Download Page 3

24 VAC 1 (HOT)

24 VAC 2 (NEUTRAL)

Inputs

l1 and l2 Power input - Both sides of the external power supply 

for the thermostat and controlled devices.

outside air temperature sensor (Optional) - This input will con

-

nect to a PECO standard 10K thermistor.  

Zone temperature remote Probe input / Condensate over-

flow

 (Optional) - This input will connect to a 10K thermistor. A low 

level switch may also be connected to this input with or without 

the thermistor. Switch closure indicates overflow.

occupancy sensor input (Optional) - The Occupancy sensor is 

a low-level switch that is open when occupied and closed when 

unoccupied. 

door switch / setback input (Optional) - This input is assigned 

to Door Switch when jumper JP3 is placed.  The Door Switch is 

a low-level switch that is open when the door is open and closed 

when the door is closed. This input is assigned to Setback when 

jumper JP3 is removed. The Setback input sensor is a low-level 

switch that is closed to signal Setback and open for normal opera

-

tion.

relative Humidity input (Optional) - This input is connected to 

a separate humidity transducer on the circuit board (not shown 

in the wiring diagram), that provides a DC signal to indicate the 

relative humidity.  

Outputs

 

Each output is connected to the L1 connection when enabled. Each 

output device is returned to the L2 connection.

y1 first stage Compressor - Output cycles with an Active 

Demand for Heating or Cooling and disables when an Active 

Demand seizes.

y2 second stage Compressor - Output is enabled if an active 

demand has been present for a minimum of 10 minutes and the 

temperature is equal to or greater than 2°F from the Set Point.  

The 2nd Compressor Stage can only be enabled or disabled if 1st 

Compressor Stage is enabled.  

reversing Valve - This output is enabled with an Active Demand 

for Cooling and disabled with an Active Demand for Heating.  

Default setting can be changed in the Service Menu 11 to reverse 

the logic.  

Dehumidification / Humidification / Outside Air

 - This output 

can be configured for Dehumidification, Humidification, or Outside 

Air operation.  A humidity sensor module must be connected to 

the PCBA for the humidity control to function. If you are installing 

a TH70-001, only the Outside Air Economizer feature is available.

fan or fan low - This output is enabled by manual user selec

-

tion or through Auto Fan Selection microprocessor operation. The 

Fan is enabled either continuously or with active demand. When 

Fan High is an available selection and is enabled, this output is 

disabled.

fan High or aux Heat - This output can be configured for either 

Fan High or Aux Heat through the service menu.  Default is Aux 

Heat.  When the system is operating in AUTO mode, the Aux 

Heat output is enabled when the room temperature is equal to 

or greater than 3°F from the temperature Set Point and after the 

time delay is met in Service Menu 18.  Fan High is selected by 

manual user selection or through Auto Fan Selection.  The Fan 

High is enabled either continuously or with active demand.

   

DESCRIPTION

Y1 

1st Stage Compressor

Y2 

2nd Stage Compressor

Reversing Valve

Provides Humidification, Dehumidification, or Outside Air    

 

based on configuration

Fan 

 

 

G1 

Fan Lo  

Aux. Heat 

 

G2 

Fan High

OR

 

 

 

 

 

System Check-Out

After wiring and installation is complete, energize the system.  

Set fan to ON.  Select each fan speed (if available) to verify 

operation.

Set the System button to AUTO, or available selection.

Using the UP arrow, adjust temperature more than 5°F above the 

current room temperature to cycle on heating.

Using the DOWN arrow adjust the Set Point to 5°F below current 

room temperature to cycle on cooling.

tHerMostat ConfiGuration / serViCe Menu

Please refer to page 6 for service menu table.

To enter the Service Menu press the UP and DOWN arrows 

simultaneously for five (5) seconds.  The current display icon will 

turn off and Service Menu 1 will be displayed.

Push the SYSTEM button to move through Service Menu items 

1-22.  

The UP and DOWN arrow keys will scroll through the range of op

-

tions for each Service Menu feature.  The selection that is flashing 

is the one you are selecting.  

All changes to the Service Menu are automatically saved when 

the system times out.

1.

2.

3.

4.

1.

2.

3.

4.

© COPYRIGHT 2008 PECO, INC.  ALL RIGHTS RESERVED. 

 

 

 

 

 

P/N 69290 3220-2088  REV 0  PAGE 3

Summary of Contents for TH170

Page 1: ...ly to 24VAC oper ated humidifiers No other connection or interlock is required Several installer selectable operating modes are available as described in the Humidity Control Operation Section Dehumid...

Page 2: ...3 When installed the TH170 Heating and cooling setback limits are used as temperature control points Fan operation in setback is cycled with demand Pressing any button will override setback for 1 hour...

Page 3: ...on or Outside Air operation A humidity sensor module must be connected to the PCBA for the humidity control to function If you are installing a TH70 001 only the Outside Air Economizer feature is avai...

Page 4: ...tion of Humidify or Dehumidify must be made in Service Menu 12 to allow the adjustment of RH Set Point If Outside Air operation is selected from Service Menu 12 instead of Humidifi cation or Dehumidif...

Page 5: ...elay is extended to 10 minutes The time delay can only be extended once If the thermostat is powered up in the Occupied State and the door is open after 10 minutes the thermostat will disable its outp...

Page 6: ...of 58 90 F A user selection of OFF will disable the Cooling Setback Zone Temperature offset adjusts the sensed Zone Temperature reading Allows you to choose what the occupant can adjust on the TH170...

Page 7: ...increases equal to or greater than the selected OA value Heat Pump operation is enabled and Aux Heat operation is disabled The Aux Heat output may still be enabled if a valid Aux Heat demand exists H...

Page 8: ...COPYRIGHT 2008 PECO INC ALL RIGHTS RESERVED P N 69290 3220 2088 REV 0 PAGE 8...

Reviews: