Peco TA155 Installation Instructions Download Page 2

© Copyright 2010 PECO, Inc. All Rights Reserved P/N 68798 3220-1449 Rev2          Page 2

White with Orange Stripe 

 

 

Fan High

White with Red Stripe  

 

 

Fan Medium

White with Brown Stripe 

 

 

Fan Low

Red 

 

 

 

 

Heat

Blue 

 

 

 

 

Cool

Black 

 

 

 

 

L1

Yellow 

 

 

 

 

L2 or Neutral

Orange   

 

 

 

Switched Power

Violet 

 

 

 

 

Fan Supply

Brown 

 

 

 

 

Remote Probe 1

Brown 

 

 

 

 

Remote Probe 2

 

 

 

 

 

*If applicable

applIcatIon notes

 RatInGs

1. To use a remote sensor, remove jumper JP-1 to disable local sensing.   

 

 

Failure to remove Jp-1 when using a remote sensor will cause 

improper operation of the thermostat. some units do not have 

remote sensing capability.

2. Remote probe wiring should be located away from any electrical 

motors or power wiring

3. Some units are internally wired for permanent fan continuous 

operation. 

4. On units with a Fan Supply input the operation of the fan is 

determined by wiring connection. For fan continuous, jumper the Fan 

Supply input (TB2-5) to the Switched Power output (TB3-3).

5. For fan cycling operation with a call for heat or cool, a fan relay must 

be used.

6. Observe electrical ratings. Thermostatic outputs are pilot duty only.

WIRInG connectIons

 WIRInG dIaGRam

Voltage

Rating 

Inductive

FLA

LRA

Resistive

Amps

Pilot

Duty 

Thermostatic

Switching

24 VAC

120 VAC
240 VAC
277 VAC

N.A.

N.A.

N.A.

24 VA

10 VA

5.8

34.8

6.0

125 VA

20 VA
20 VA
20 VA

125 VA
125 VA

2.9

17.4

5.0

2.4

14.4

4.2

FAN AND SYSTEM SWITCHES

caUtIon

!