© Copyright 2010 PECO, Inc. All Rights Reserved P/N 68798 3220-1449 Rev2 Page 2
White with Orange Stripe
Fan High
White with Red Stripe
Fan Medium
White with Brown Stripe
Fan Low
Red
Heat
Blue
Cool
Black
L1
Yellow
L2 or Neutral
Orange
Switched Power
Violet
Fan Supply
Brown
Remote Probe 1
Brown
Remote Probe 2
*If applicable
applIcatIon notes
RatInGs
1. To use a remote sensor, remove jumper JP-1 to disable local sensing.
Failure to remove Jp-1 when using a remote sensor will cause
improper operation of the thermostat. some units do not have
remote sensing capability.
2. Remote probe wiring should be located away from any electrical
motors or power wiring
3. Some units are internally wired for permanent fan continuous
operation.
4. On units with a Fan Supply input the operation of the fan is
determined by wiring connection. For fan continuous, jumper the Fan
Supply input (TB2-5) to the Switched Power output (TB3-3).
5. For fan cycling operation with a call for heat or cool, a fan relay must
be used.
6. Observe electrical ratings. Thermostatic outputs are pilot duty only.
WIRInG connectIons
WIRInG dIaGRam
Voltage
Rating
Inductive
FLA
LRA
Resistive
Amps
Pilot
Duty
Thermostatic
Switching
24 VAC
120 VAC
240 VAC
277 VAC
N.A.
N.A.
N.A.
24 VA
10 VA
5.8
34.8
6.0
125 VA
20 VA
20 VA
20 VA
125 VA
125 VA
2.9
17.4
5.0
2.4
14.4
4.2
FAN AND SYSTEM SWITCHES
caUtIon
▲
!