Peco TA155 Installation Instructions Download Page 1

1.  Install the T155 with the two furnished mounting screws to a 

standard 2” x 4” electrical box, 4-11/16” x 2-1/8” square device box 

with a 2” x 4” adapter ring or to a 4” x 4” box with accessory adapter 

plate.

2. For wall installations, mount the thermostat on an inside wall 

approximately 5 feet above the floor.  The location should provide 

circulation at average room temperature.  Avoid direct sunlight or 

sources of hot or cold air in the room or wall.

3. Remove the knob and then the cover.  Mount thermostat base 

assembly to the outlet box using the screws provided, tighten the 

screws evenly but do not over tighten. Make wiring connections as 

noted.

4. To use a remote sensor, remove jumper JP-1 to disable local 

sensing.  Failure to remove JP-1 when using a remote sensor will 

cause improper operation of the thermostat. Some units do not have 

remote sensing capability. See Application Notes.

5. Reinstall the cover assembly.  Install cover locking screw provided. 

Reinstall the knob.

©  Copyright  2010  PECO,  Inc. All  Rights  Reserved  P/N  68798  3220-1449  Rev2  Page  1

Installation Instructions

TA155/TB155

Knob Removal and Replacement

InstallatIon

• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO 

INSTALL, OPERATE OR SERVICE THIS THERMOSTAT. 

• Failure to observe safety information and comply with instructions could 

result in PERSONAL INJURY, DEATH  AND/OR PROPERTY DAMAGE.

• To avoid electrical shock or damage to equipment, disconnect power before 

installing or servicing.

• To avoid electric shock or damage to equipment, use only wiring with insula-

tion rated for full thermostat operating voltage.

• To avoid potential fire and/ or explosion do not use in potentially flammable or 

explosive atmospheres.

• Retain these instructions for future reference.  This product, when installed, 

will be part of an engineered system whose specifications and performance 

characteristics are not designed or controlled by PECO, Inc.  You must 

review your application and national and local codes to assure that your 

installation will be functional and safe. 

Temperature Range: 50°F - 90°F (10°C - 32°C)

TA155: A HEAT-OFF-COOL system switch manually selects heating 

or cooling mode. In the HEAT position, only the heat output cycles 

with demand. In the COOL position, only the cool output cycles with 

demand. In the OFF position, heating and cooling outputs are off. Units 

with a two position system switch or without a system switch must use 

a load transfer switch when both heating and cooling outputs are used. 

This prevents control failure and equipment damage caused by direct 

cycling between loads.

TB155: An ON-OFF system switch enables auto-changeover of heating 

and cooling modes. In the ON position the thermostat activates heating 

or cooling outputs dependant upon the relationship between set point 

and ambient temperature. Heat on to cool on dead band is 4°F. In 

the OFF position, heating and cooling outputs are off.  Units without 

a system switch cycle between heating and cooling with a 4°F dead 

band.

FAN: Some units have a switch for manual selection of fan speed. On 

these units fan operation is either internally wired for fan continuous 

operation or is dependant upon connection to the fan supply input. 

When internally wired for fan continuous operation, the fan will be 

off when the system switch is off. When dependant upon external 

connections the fan may not be off with the system switch in the off 

position. The fan supply input is switched to fan speed outputs (HI - 

MED - LO).

SWITCHED POWER: L1 power is switched to this output any time the 

system switch is out of the OFF position.

 tHeRmostat opeRatIon

When removing and re-installing the T-155 

knob, care must be taken. 

• Align arrow to 70°F on the knob (22C) or 

midrange when removing the knob.

• Reinstall knob by aligning arrow to 70°F 

(22C) or midrange. 

• Do not force it. When properly aligned, the 

knob will slip into position. 

Align arrow to 70°F  

on the knob (22C)

• Use Copper wire 

only, insulate or wire 

nut all unused leads.

• Any wiring, including 

the remote probe, 

may carry the full 

operating voltage of 

the thermostat.

caUtIon

!

caUtIon

!

WaRnInG

!