1. INTRODUCTION
This user manual provides information on product features and guides you through all basic functions.
1.1. DESCRIPTION
The
FT-1003
Air Volume transducer sensor operates on the capacitance principal and is capable of
sensing ultra low differential pressures. In the capacitance cell, a very lightweight, responsive
diaphragm deflects a small amount when pressure is applied. This deflection results in a change in
capacitance, which is then detected and processed electronically into an output signal linear to the
velocity pressure. The electronic signal is then sent to the square root extractor/multiplier, which
converts the velocity pressure signal into an analog output signal linear to velocity (fpm) or volume
(cfm).
An integral red LED indicator verifies proper power supply wiring orientation.
1.1.1. Installation
Setup
Refer to figures below for pressure and electrical connections.
ELECTRICAL CONNECTIONS
STATUS
POWER
LOW
HIGH
-
18 TO 36VDC
POWER SUPPLY
+
DPT
TP2
PRESSURE CONNECTIONS
RECEIVER
-
INCORPORATED
CONTROLS
PARAGON
+
PCI
-
+
GND
TP1
SPAN
ZE
R
O
ZE
R
O
DP
T
SP
AN
HIGH (TOTAL)
LOW (STATIC)
SIG
(0-5/10VDC)