PCE Instruments PCE-IT100 User Manual Download Page 10

 

 

 

©  PCE Instruments 

 

Turn on meter 

To turn on the meter, select the desired function by turning the rotary switch. The meter will power 
on directly. To turn off the 

meter, select “OFF“ with the rotary switch. 

Connect the test leads 

Connect the red test lead to the V

Ω input jack. Connect the black test lead to the COM input jack. 

6.1 

Set zero point 

To reset the zero point, choose 

“400Ω“ with the rotary switch. Now hold the measuring tips against 

each other. Then press 

“ZERO“. The zero point has been reset. 

Note: 

Zeroing is only valid for the 

“400Ω“ measurement and expires when you select a different 

measuring function. 

Insulation measurement 

To make an insulation measurement, select the desired voltage with the rotary switch. Here you 
can select a test voltage of 125 V, 250 V, 500 V or 1000 V. Now connect the test leads to your 
sample.  Press  the  TEST  key  to  generate  the  desired  test  voltage  directly.  To  make  a 
measurement, press and hold the TEST key. The measurement is finished when you release the 
key. Bear in mind that some residual voltage may be present in the meter. 
The reading will be shown in the upper part of the display. The test voltage is shown in the lower 
part of the display. The measurement range is selected by the meter automatically. 

Note: 

If the sample carries a voltage of at least 30 V, the meter will display 

“>30 V“ and “ “, a 

beep sound will be audible and the meter will not make a measurement. Therefore, it is important 
to remove any external voltages before each measurement. 

7.1 

Measuring AC motors 

Interrupt the voltage supply of the motor by disconnecting the connection cable of the motor. In 
case there are switches on the motor, these must be turned on. To measure the insulation now, 
connect one test lead to the supply cable and the other one to the motor. 

7.2 

Measuring DC motors 

Interrupt the voltage supply of the motor by disconnecting the connection cable of the motor. In 
case there are switches on the motor, these must be turned on. Now connect one test lead to the 
PE connection of the connection cable and the second one to, for example, the carbon brushes 
to measure the insulation. 

7.3 

Measuring insulated cables 

To  measure  the  insulation  of  a  cable,  make  sure  that  the  cable  ends  are  open.  Now  make  a 
measurement by measuring each cable core with every other cable core. 
 
 

 

Summary of Contents for PCE-IT100

Page 1: ...sulation Tester User Manual User manuals in various languages fran ais italiano espa ol portugu s nederlands t rk polski can be found by using our product search on www pce instruments com Last change...

Page 2: ...o point 8 7 Insulation measurement 8 7 1 Measuring AC motors 8 7 2 Measuring DC motors 8 7 3 Measuring insulated cables 8 8 Continuity test resistance measurement 9 9 Voltage measurement AC DC 9 10 Au...

Page 3: ...es from PCE Instruments or equivalent Before each use inspect the case for visible damage If any damage is visible do not use the device Do not use the instrument in explosive atmospheres The measurem...

Page 4: ...ons on the meter which mean the following This icon can be found next to another symbol or a connection and is a reference to the user manual This icon indicates that high voltage could be present Sho...

Page 5: ...ts in commercial buildings Motors switches sub distributors in a three phase circuit light circuits in commercial buildings supply cables for industrial plants electrical appliances or connections nea...

Page 6: ...0 00 400 0 Resolution 0 01 0 1 Accuracy 1 2 3 digits Overvoltage protection 250 V RMS Measuring voltage max 5 8 V Continuity test Icon Resolution 0 01 Audible signal 35 Short circuit current 200 mA Ov...

Page 7: ...ment at 250 V 0 10 Measurement range 0 250 4 000 M 4 001 40 00 M 40 01 400 0 M 400 1 4000 M Resolution 0 001 M 0 01 M 0 1 M 1 M Accuracy 2 10 digits 2 10 digits 5 5 digits 4 5 digits Test current 1 mA...

Page 8: ...st Audible signal at resistance 35 Battery indication is displayed when battery voltage is no longer sufficient Excess of measurement range OL is displayed Sampling rate 2 5 measurements s 0 4 Hz Zero...

Page 9: ...truments 7 4 Device description 1 LCD 2 MAX MIN HOLD key 3 LOCK key 4 Zero point and backlight key 5 TEST key 6 Rotary function switch 7 V input jack 8 Ground input jack 9 Strap holder 10 Battery comp...

Page 10: ...sent in the meter The reading will be shown in the upper part of the display The test voltage is shown in the lower part of the display The measurement range is selected by the meter automatically Not...

Page 11: ...es of inactivity This function cannot be disabled To turn on the meter again after auto power off turn the rotary switch back to OFF and then turn it o the desired position 11 Keys The meter has four...

Page 12: ...ttery compartment at the rear side the cover of which is affixed with four screws Remove all batteries You can now replace the fuse Only use an FF 500 mA 1000 V fuse 15 Warranty You can read our warra...

Page 13: ...583 975 114 Fax 49 0 2903 976 99 9971 Fax 44 0 2380 98703 9 Fax 39 0583 974 824 info pce instruments com info pce instruments co uk info pce italia it www pce instruments com deutsch www pce instrumen...

Reviews: