![PCB Piezotronics 685B0001A13 Installation And Operating Manual Download Page 30](http://html1.mh-extra.com/html/pcb-piezotronics/685b0001a13/685b0001a13_installation-and-operating-manual_1515380030.webp)
1
1
2
2
3
3
4
4
A
A
B
B
C
C
D
D
CODE
IDENT. NO.
52681
DWG. NO.
SCALE:
SHEET
DRAWN
CHECKED
ENGINEER
TITLE
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
DECIMALS X
.05
XX
.01
XXX
.005
ANGLES ± 2 DEGREES
FILLETS AND RADII .003 - .005
HEX DIMENSIONS ARE:
≤
.5 + .000 / - .003
> .5 + .000 / - .005
REMOVE ALL BURRS
SHARP = R.000 - R.003
INTERNAL THREAD DEPTH MIN.
3425 WALDEN AVE. DEPEW, NY 14043
(716) 684-0002 E-MAIL: [email protected]
37476
CSA APPROVAL
685B0X01A1X & CS685YZZZ
INTERCONNECTION
1 OF 2
NONE
XXXX
.0005
JDM
7/17/17
JDM
7/17/17
GGS
7/17/17
POWER SUPPLY
4-20mA/15Vdc OUTPUT
85 to 245Vac 50/60Hz
150mA MAXIMUM
ALARM RELAY
SPDT
10Aac/5Adc 245Vac/30Vdc MAXIMUM
ALERT RELAY
SPDT
10Aac/5Adc 245Vac/30Vdc MAXIMUM
REMOTE RESET 5Vdc/1mA
MOMENTARILY CONNECT
RESET TO COMM
RAW VIBRATION OUTPUT
100mV/G
10G MAXIMUM
+AC
-AC
GND
NC/DE
COMM
NO/DE
NC/DE
COMM
NO/DE
POS.
NEG.
SHLD.
RESET
COMM
SHLD.
POS.
NEG.
SHLD.
NON-HAZARDOUS / SAFE AREA
OR DIV 2 / ZONE 2
CONDUIT/CABLE
POWER SUPPLY
SIGNAL CONDITIONER
HAZARDOUS AREA
DIV 2
VIBRATION SWITCH
PN CS685YZZZ
VIBRATION SWITCH
PN 685B0X01A1X
37
47
6
PCB Piezotronics Inc. claims proprietary rights in
the information disclosed hereon. Neither it nor any
reproduction thereof will be disclosed to others
without the written consent of PCB Piezotronics Inc.
THE INSTALLER SHALL INSURE THAT THE TOP COVER INTERNAL GASKET AND CONDUIT
HUB THREADS ARE COATED WITH SUPPLIED SILICON GREASE TO MAINTAIN TYPE
4X/NEMA 4X INTEGRITY.
THE RELAY OUTPUTS MAY BE CONNECTED TO DIFFERENT PHASES ONLY FOR VOLTAGES
UP TO 125VAC. FOR VOLTAGES ABOVE 125VAC THE RELAYS SHALL BE CONNECTED
TO SAME PHASE CIRCUITS ONLY.
IF ONLY ONE CONDIT ENTRY IS USED, THE UNUSED ENTRY MUST BE SEALED WITH A FITTING
COMPLIANT TO HAZARDOUS RATINGS AS REQUIRED BY THE APPLICATION AND LOCAL
GOVERNING AGENCY.
INTERNAL GROUND SCREW MUST BE CONNECTED TO POWER SUPPLY GROUND WITH
WIRE SIZE EQUAL TO OR GREATER THAN 14 AWG.
ALL CONDUIT AND JUNCTION BOXES MUST MEET THE CLASS, DIVISION, GROUP, AND
INSTALLATION METHOD AS REQUIRED BY THE APPLICATION AND LOCAL
GOVERNING AGENCY.
SHIELDS TO BE EARTHED AT POWER SUPPLY END.
THE INSTALLER SHALL INSURE THAT THE VIBRATION SWITCH MOUNTING STRUCTURE IS AT
THE SAME GROUNDING POTENTIAL AS THE SUPPLY SOURCE GROUND. TOTAL EARTH
LOOP IMPEDANCE SHALL BE LESS THAN ONE OHM.
4.) FOR GUIDANCE ON CANADIAN INSTALLATION, REFER TO CEC PART I.
FOR GUIDANCE ON U.S. INSTALLATION, INSTALL IN ACCORDANCE WITH
NEC [ANSI/NFPA70] AND [ANSI/ISA RP12.6].
3.) CERTIFIED BY THE APPROPRIATE APPROVAL AUTHORITY FOR INSTALLATION IN THE
FOLLOWING AREAS:
CLASS 1, DIV 2, GROUPS A,B,C,D
CLASS 1, ZONE 2, GROUPS IIC T6
2.) WIRING (685B0X01A1X) & CS685YZZZ:
MULTICONDUCTOR
.5in [12.7mm] X 1000ft [305m] MAX.
1.) PART NUMBERS IS 685B0X01A1X WHERE X INDICATES RANGE, FREQUENCY RESPONSE,
AND NUMBER OF CONDUIT HUBS. 685B0X01D1X DENOTES INSTALLED MOUNTING PLATE.
NO CHANGES WITHOUT CSA APPROVAL
SCHEDULE DRAWING
NO MODIFICATIONS PERMITTED
WITHOUT REFERENCE TO THE
NOTIFIED BODY
7
8
11
5
11
11
9
11
7
8
11
5
6
10
10
REVISIONS
REV
DESCRIPTION
DIN
A
ADDING CS685YZZZ
46985
WARNING - EXPLOSION HAZARD
DO NOT DISCONNECT EQUIPTMENT
UNLESS POWER HAS BEEN SWITCHED
OFF OR THE AREA IS KNOWN TO BE
NON-HAZARDOUS
5
6
7
8
9
10
11
AVERTISSEMENT - RISQUE D'EXPLOSION
NE PAS DÉCONNECTER L'ÉQUIPEMENT
À MOINS QUE LA PUISSANCE SOIT
COMMUTE OFF OU LA ZONE EST
CONNUE POUR ÊTRE NON DANGEREUX