Basic Operation

WARNING

CAUTION

Service on this boiler should be undertaken only by trained and skilled personnel from a
qualified service agency

.

Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the
electrical supply to the pump. Instead, shut off the gas supply at a location external to the
appliance.

Do not use this boiler if any part has been under water. Immediately call a qualified service
agency to inspect the boiler and to replace any part of the control system and any gas control
which has been under water.

A. General.

This water boiler is an induced draft appliance and is equipped with controls for proper

operation. All controls must be in proper working order. Contact a qualified service agency to provide
annual maintenance as specified in Installation, Operation and Maintenance Manual.

1.

Limit.

See Figure 1. A Device which automatically interrupts boiler operation when the water

temperature exceeds the set point. Maximum temperature setting is 220°F (104°C).

Original equipment with this boiler is a Honeywell L4080. Boiler operation is interrupted when
system temperature reaches cut-out temperature. Boiler operation resumes automatically when
system temperature falls approximately 15°F (8°C) below the cut-out temperature.

2.

Flame Rollout Switch.

See Figure 1. A device which automatically interrupts boiler operation

when flames or excessive heat are present in the combustion area. The control is a single use
device. If the control is activated to interrupt boiler operation, do not attempt to place boiler in
operation. Contact a qualified service agency.

3.

Pressure Switch.

See Figure 1. A device which automatically interrupts boiler operation when

there is a blockage in the vent pipe. The control is located in the boiler vestibule. The control is an
automatic reset device. If the control is activated to interrupt boiler operation, do not attempt to
place boiler in operation. Contact a qualified service agency.

4.

Pilot.

The pilot provides the ignition source for the main burners. Your boiler has an intermittent

pilot. The pilot ignites only when there is a call for heat and extinguishes when the call for heat
ends. See Figures 1 and 3.

5.

Gas Valve.

The gas valve monitors pilot flame and regulates gas flow to the main burners and 

pilot. See Figure 1. 

6.

Safety Relief Valve.

A device which protects the boiler against excessive pressure. The safety

relief valve can discharge a large amount of hot water - the installer should provide piping to
discharge water near floor at a floor drain. If the safety relief valve discharges water, follow
instructions TO TURN OFF GAS TO APPLIANCE (see Figure 2), and contact a qualified service
agency.

2