DIMENSIONS — OUTDOOR UNIT
DIMENSION CHART
UNIT
UNIT WITH ALUMINUM-FIN COIL
DIM. A
DIM. B
PH1S090
1
8
-8
9
[508.0]
1
8
-5
9
[431.8]
WEIGHT (WITH ALUMINUM-FIN COIL)
STD UNIT
CORNER W
CORNER X
CORNER Y
CORNER Z
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
540
245
132
60
100
45
133
60
175
80
SERVICE VALVE CONNECTIONS
UNIT
SUCTION
LIQUID
PH1S090
1
1
⁄
8
9
[28.6]
1
⁄
2
9
[12.7]
ELECTRICAL CONNECTIONS
CONNECTION SIZES
AA
1
3
⁄
8
9
Dia. [35] Field Power Supply Hole
BB
2
9
Dia. [51] Power Supply Knockout
CC
2
1
⁄
2
9
Dia. [64] Power Supply Knockout
DD
7
⁄
8
9
Dia. [22] Field Control Wiring Hole
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Center of gravity. See Chart for dimensions.
3.
Direction of airflow.
4. Minimum clearance (local codes or jurisdiction may prevail).
a. Bottom to combustible surfaces: 0 in.
b. Condenser coil, for proper airflow: 36 in. one side, 12 in. the other. The
side getting the greater clearance is optional.
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Between units: Control box side, 42 in. per NEC (National Electrical
Code).
e. Between unit and ungrounded surfaces: Control box side, 36 in. per
NEC.
f. Between unit and block or concrete walls and other grounded surfaces,
control box side, 42 in. per NEC.
5. With the exception of the clearance for the condenser coil as stated in
note 4b, a removable fence or barricade requires no clearance.
6. Units may be installed on combustible floors made from wood or class A, B,
or C roof covering material.
PH1S090
8