Boxed Power Supply assembly
Instruction set
Figure 8 mains lead
fk1-099
3
Pozi pan self tapping screw - zinc
3
Wall Plugs
1
Cable gland
1
Cable gland lock nut
1
IN4001 Diode
10
Cable tie
4
Cable clip
1
Rubber washer
1
M4 Pan head screw
4
PCB pillar
-20 °C
+45 °C
13V DC
13.8V DC
2 A
1 A
100V AC
240V AC
+/- 10%
1.2 A
50 Hz
60 Hz
+/- 3 Hz
232mm
320mm
80mm
236mm
320mm
80mm
150mm
100mm
62mm
Specifications
Operating temperatures - all items
PSU Electrical
Output voltage
Maximum load output current
Maximum battery charging current
Mains supply voltage
Mains supply current
Mains supply frequency
Environment
Metal Cabinet
Plastic Cabinet
Battery Compartment (Plastic Housing)
Dimensions
:
The following warnings and instructions MUST be adhered to. Read the instructions before installing and powering the
equipment. Keep the instructions in a safe place for future reference.
:
RECEIVING INSPECTION-
Remove any traces of packing material from the unit as such debris may create a fire or shock hazard.
Unpack the unit with care and inspect for transit damage. If damage is suspected, the unit must not be used or tested, but should be
returned to Paxton for investigation and the damage reported to the carrier.
:
INSTALLATION-
Only qualified and trained personnel, familiar with this type of product and who fully understand these instructions
should install, connect or test this equipment. There are no user serviceable parts within the PSU unit.
:
-
The equipment is intended for indoor use only in dry locations. This is a Class A product. In a domestic environment this product
may cause radio interference in which case the user may be required to take adequate measures.
:
-
The installation must meet National Wiring Regulations and IEC60950-1 standards.
:
-
Disconnect Devices: A readily accessible disconnect device shall be incorporated in the building wiring to include an appropriately
rated circuit breaker to disconnect both poles with at least a 3.0 mm contact gap. After switch off, all internal capacitors will discharge
to safe levels within 60 seconds under normal conditions. Under fault conditions, charge may be held for much longer and suitable
precautions should be taken before handling the unit.
:
-
Protection device: The fusing characteristics of the protection device to be used are T3.15AH250V
WARNINGS
Min
Max
Width
Height
Depth
Waterproof
No
Min
Max
Features
Battery backup
Fast/Trickle charge
Deep discharge protection
Mains failure alarm (PSU)
Tamper alarm
The cabinet can accommodate a 12V / 7Ah battery.
The battery is continuously charged to keep it at maximum capacity.
If battery voltage falls below 9.5V, it will automatically disconnect - Red LED goes out.
This pair of voltage free contacts goes open circuit if the mains power fails.
The tamper switch has voltage free contacts that go open circuit if the lid is opened.
Contents in box
Description
Qty
Fitting kit