Heat exchange
Arrangement / Opt. functions / Add new function... / Heat exchange
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Sen. Source Heat source sensor selection system dependent
system dependent
Sen. Sink
Heat sink sensor selection
system dependent
system dependent
D
Ton
Switch-on temperature
difference
2.0 … 30.0 K
6.0 K
D
Toff
Switch-off temperature
difference
1.0 … 29.0 K
4.0 K
DΤ
set
Set temperature difference
1.5 … 40.0 K
10.0 K
Min. speed
Minimum speed
(20) 30 … 100 %
30 %
Tmax
Maximum temperature of
the store to be loaded
10 … 95 °C
60 °C
Tmin
Minimum temperature of
the store to be loaded
10 … 95 °C
10 °C
Timer
Timer
-
-
Days of the
week
Day selection
All days, Monday …
Sunday, Continue
-
Timer
Time frame adjustment
00:00 … 23:45
-
Funct.
Activation / Deactivation
Activated, Deactivated Deactivated
The Heat exchange function can be used for transferring heat from a heat source
to a heat sink.
The allocated relay is energised when all switch-on conditions are fulfi lled:
• the temperature difference between the allocated sensors has exceeded the
switch-on temperature difference
• the temperature at the heat source sensor has exceeded the minimum tem-
perature
• the temperature at the heat sink sensor has fallen below the maximum tem-
perature
When the Set temperature difference is exceeded, pump speed control starts.
For every deviation of 2 K, the pump speed will be adjusted by 10 %.
When the Timer option is activated, a timer is indicated in which time frames for
the function can be adjusted.
Note:
For more information about timer adjustment, see page 11.
Sen. Source
Sen. Sink
Relay