36
Master Controller X1 terminal
Wire of boost ventilation key cable
X1.12
Wire 1
X1.13
Wire 2 (GND)
Table 22: Terminal assignment of boost ventilation key connection
Connecting external sensors
The operating mode
Automatic sensor
of the automatic mode is controlled by an analogue sensor signal that is
generated by one or several sensors. To establish the connection between the sensor module and Master Controller
terminal X2, use the type of cable stipulated for transmitting the sensor signal. The cable is inserted into the FOCUS
through one of the pre-cut cable guides.
Master Controller X2 terminal
Sensor module cable wire
X2.7 (analogue input1)
Wire 1(sensor signal 0–10 V or 4–20 mA)
X2.8 (GND)
Wire 2 (GND)
Table 23: Terminal assignment of analogue sensor signal connection
Connecting the status relay
A status relay on the Master Controller signals the operating status of the fans (factory setting).
Fan off: contacts open
Fan on: contacts closed
Master Controller X1 terminal
Contact designation
X1.9
Status relay make contact (max. 24 V switching voltage)
X1.10
Status relay two-way contact (max. 24 V switching voltage)
Table 24: Terminal assignment of status relay connection
Connecting external release
The operation of the system can be activated or deactivated by an external release signal. The potential-free release
contacts are located next to the terminal X1 and are bridged ex-factory.
Master Controller X1 terminal
Contact designation
X1.14
External release
X1.15
External release (GND)
Table 25: Terminal assignment of external release connection
When the bridge is removed and there is no external release, the following displays are generated:
TFT control panel
LED control panel
L1 and L7 light up
Table 26. Display of no external release
Connecting digital inputs and outputs
The digital inputs and outputs DIO1 and DIO2 can only be programmed with the configuration software. At the
factory, the following parameters are specified:
DIO1: Activate automatic (as a digital input signal)
DIO2: General message (as a digital output signal)
Master Controller X2 terminal
Contact designation
X2.1
Digital input or output 1 (can be parametrised)
X2.2
Digital input or output 1 (GND)
Summary of Contents for FOCUS 200 Base
Page 1: ...Translation of the original instruction manual Heat Recovery Unit FOCUS F 200...
Page 49: ...49 Dimensions Fig 43 Dimensional drawing FOCUS...
Page 50: ...50 FOCUS circuit plan Fig 44 Terminal assignment circuit diagram FOCUS...
Page 51: ...51 Master Controller terminal assignment Fig 45 Master Controller terminal assignment...