19
Fig. 8: Automatic mode automatic timer with active fan speed FS2
4.3.2.4.2
Automatic sensor
The operating mode
Automatic sensor
of the automatic mode requires the connection of an outdoor air quality / CO
2
or moisture sensor to the control of the ventilation unit. The analogue signal of the sensor is interpreted as a control
signal for the rotational fan speed of the ventilation unit. When applying several sensors in a ventilation system, the
output signal of a maximum value module will be used to control the ventilation unit.
First, the navigation buttons (red text background) and check marks are used to select whether the sensor is
equipped with a power or voltage output (Electrical power: 4...20 mA, voltage: 0...10 V) and confirmed via Enter.
Then the lowest point (characteristic curve start value p1) and the highest point (characteristic curve end value p2) of
a characteristic curve assumed to be linear between these two points for the fan speed are parametrised between
17% and 100%. The nominal values (red text background) to be parametrised can be selected with the navigation
buttons and the values adjusted with the +/
- buttons.
Symbol Description
Sensor output signal
0…10 V characteristic curve
4…20 mA characteristic curve
Characteristic
curve start
value
Umin (V)
≙
n_min (%)
lmin (mA)
≙
n_min (%)
Characteristic
curve end
value
Umax (V)
≙
n_max (%)
Imax (mA)
≙
n_max (%)
U-n characteristic curve diagram
l-n characteristic curve diagram
Table 11: Automatic sensor parametrisation
Plausibility check for sensors with power output:
•
Concerns: Input A1 on the master controller (configured as 4...20 mA input)
•
Error message if at the input a value of 0...3 mA is present for more than 1 s
•
Reset of the error if I > 3.5 mA for at least 1 s
4.3.2.5 Sub-menu Date/time
In this menu the date and time are set. The nominal values (red text background) to be parametrised can be selected
with the navigation buttons and the values adjusted with the +/
- buttons.
4.3.2.6 Sub-menu Language selection
In this menu, the local language for the TFT control panel can be selected via the navigation buttons.
4.3.2.7 Sub-menu Screen dimming
In this menu, individual screen brightness and the duration until the dimming takes effect after non-operation can be
adjusted using the navigation buttons.
•
Duration until dimming in 1 min increments
•
Dimming in 5% increments
Summary of Contents for FOCUS 200 Base
Page 1: ...Translation of the original instruction manual Heat Recovery Unit FOCUS F 200...
Page 49: ...49 Dimensions Fig 43 Dimensional drawing FOCUS...
Page 50: ...50 FOCUS circuit plan Fig 44 Terminal assignment circuit diagram FOCUS...
Page 51: ...51 Master Controller terminal assignment Fig 45 Master Controller terminal assignment...